EasyManuals Logo

Lennox LRP16G User Manual

Lennox LRP16G
30 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #19 background imageLoading...
Page #19 background image
Page 19
Ignition Control LED Codes
The ignition control LED ashes codes which indicate
normal or abnormal operations:
Table 4. Fault Codes
LED Status Flashing Rate Fault Description
Slow Flash
One ash per
second
Normal operation:
No call for heat
Fast Flash
Two ashes per
second
Normal operation:
Call for heat
2 Flash
Two ashes in
second with
1-second pause
System lockout:
Failed to detect or
sustain ame
3 Flash
Three ashes in
1.5 seconds with
1-second pause
Pressure switch senses
incorrect pressure or gas
valve coil is open.
4 Flash
Four ashes in
2 seconds with
1-second pause
High limit or rollout
switch open
5 Flash
Five ashes in
2.5 seconds with
1-second pause
Flame sensed and gas
valve not energized
Steady --
Internal failure:
Micro-controller failure;
self-check