SPECIFICATIONS
Gas
Heating
Performance
Model No.
Model No. - Low NO
x
ML180DF045P24A
- - -
ML180DF045P36A
- - -
ML180DF070P36A
ML180DF070XP36A
1
AFUE 80% 80% 80%
Input - Btuh 44,000 44,000 66,000
Output - Btuh 35,000 36,000 53,000
Temperature rise range - °F 25 - 55 15 - 45 25 - 55
Gas Manifold Pressure (in. w.g.)
Nat. Gas / LPG/Propane
3.5 / 10.0 3.5 / 10.0 3.5 / 10.0
High Static - in. w.g. 0.50 0.50 0.50
Connections
in.
Flue connection - in. round 4 4 4
Gas pipe size IPS 1/2 1/2 1/2
Indoor
Blower
Wheel nom. dia. x width - in. 10 x 7 10 x 8 10 x 8
Motor output - hp 1/5 1/3 1/3
Tons of add-on cooling 1.5 - 2 2 - 3 2 - 3
Air Volume Range - cfm 401 - 1157 739 - 1524 717 - 1562
Electrical
Data
Voltage 120 volts - 60 hertz - 1 phase
Blower motor full load amps 3.1 6.1 6.1
Maximum overcurrent protection 15 15 15
Shipping Data lbs. - 1 package 105 113 128
NOTE - Filters and provisions for mounting are not furnished and must be eld provided.
1
Annual Fuel Utilization Efciency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized furnaces.
SPECIFICATIONS
Gas
Heating
Performance
Model No.
Model No. - Low NO
x
ML180DF090P36B
- - -
ML180DF090P48B
ML180DF090XP48B
ML180DF110P60C
ML180DF110XP60C
1
AFUE 80% 80% 80%
Input - Btuh 88,000 88,000 110,000
Output - Btuh 71,000 71,000 89,000
Temperature rise range - °F 35 - 65 25 - 55 30 - 60
Gas Manifold Pressure (in. w.g.)
Nat. Gas / LPG/Propane
3.5 / 10.0 3.5 / 10.0 3.5 / 10.0
High Static - in. w.g. 0.50 0.50 0.50
Connections
in.
Flue connection - in. round 4 4 4
Gas pipe size IPS 1/2 1/2 1/2
Indoor
Blower
Wheel nom. dia. x width - in. 10 x 9 10 x 10 11-1/2 x 10
Motor output - hp 1/3 1/2 1
Tons of add-on cooling 2 - 3 3 - 4 4 - 5
Air Volume Range - cfm 743 -1695 917 - 1929 1517 - 2760
Electrical
Data
Voltage 120 volts - 60 hertz - 1 phase
Blower motor full load amps 6.1 8.2 10.0
Maximum overcurrent protection 15 15 15
Shipping Data lbs. - 1 package 131 140 160
NOTE - Filters and provisions for mounting are not furnished and must be eld provided.
1