Page 24
Resize the common venting system to the minimum vent 
pipe  size  determined  by  using  the  appropriate  tables  in 
Appendix  G.  (These  are  in  the  current  standards  of  the 
National Fuel Gas Code ANSI Z223.1.
If replacing a furnace which was
commonly vented with another gas appliance, the size
of the existing vent pipe for that gas appliance must be
checked. Without  the heat of the original furnace flue
products, the existing vent pipe is probably oversized for
the  single  water  heater  or  other  appliance.  The  vent
should be checked for proper draw with the remaining
appliance.
REPLACING FURNACE THAT WAS PART OF A
COMMON VENT SYSTEM
CHIMNEY
OR GAS
VENT
(Check sizing
for water
heater only)
FURNACE
(Replaced)
WATER
HEATER
OPENINGS
(To Adjacent
Room)
FIGURE 17 
Exhaust Piping (FIGURE 18, FIGURE 20 and FIGURE 
21)
Route piping to outside of structure. Continue with instal-
lation  following  instructions  given  in  piping  termination 
section.
 CAUTION
Do not discharge exhaust into an existing stack 
or stack that also serves another gas appliance. If 
vertical discharge through an existing unused stack 
is required, insert PVC pipe inside the stack until the 
end is even with the top or outlet end of the metal 
stack.
 CAUTION
The exhaust vent pipe operates under positive 
pressure and must be completely sealed to prevent 
leakage of combustion products into the living 
space.
Vent Piping Guidelines
NOTE - Lennox has approved the use of DuraVent® and 
Centrotherm  manufactured  vent  pipe  and  terminations 
as  an  option  to  PVC. When  using  the  PolyPro®  by  Du-
raVent or InnoFlue® by Centrotherm venting system the 
vent  pipe  requirements  stated  in  the  unit  installation  in-
struction – minimum & maximum vent lengths, termination 
clearances, etc. – apply and must be followed. Follow the 
instructions provided with PoyPro by DuraVent and Inno-
Flue by Centrotherm venting system for assembly or if re-
quirements are more restrictive. The PolyPro by Duravent 
and  InnoFlue  by  Centrotherm  venting  system  must  also 
follow  the  uninsulated  and  unconditioned  space  criteria 
listed in TABLE 16.
The ML296UHV can be installed as either a Non-Direct 
Vent or a Direct Vent gas central furnace.
NOTE - In Non-Direct Vent installations, combustion air is 
taken from  indoors  or ventilated  attic  or crawlspace  and 
ue gases are discharged outdoors. In Direct Vent instal-
lations,  combustion  air  is  taken  from  outdoors  and  ue 
gases are discharged outdoors.
Intake and exhaust pipe sizing  -- Size pipe according  to 
TABLE  13 (minimum)  and TABLE 14  (maximum). Count 
all elbows inside and outside the home. Regardless of the 
diameter of pipe used,  the standard roof and wall  termi-
nations described in section Exhaust Piping Terminations 
should  be  used.  Exhaust  vent  termination  pipe  is  sized 
to optimize the velocity of the exhaust gas as it exits the 
termination. Refer to TABLE 17.
In some applications which permit the use of several dif-
ferent sizes of vent pipe, a combination vent pipe may be 
used. Contact Lennox’ Application Department for assis-
tance in sizing vent pipe in these applications.
NOTE - The exhaust collar on all models is sized to ac-
commodate  2”  Schedule  40  vent  pipe.  In  horizontal  ap-
plications,  any  transition  to  exhaust  pipe  larger  than  2” 
must be made in vertical runs of the pipe. Therefore a 2” 
elbow  must  be  added  before  the  pipe  is  transitioned  to 
any size larger than 2”. This elbow must be added to the 
elbow count used  to determine acceptable  vent lengths. 
Contact the Application Department for more information 
concerning sizing of vent systems which include multiple 
pipe sizes.