Page 35
Details of Intake and Exhaust Piping Terminations for 
Direct Vent Installations
NOTE - In Direct Vent installations, combustion air is taken 
from outdoors and ue gases are discharged to outdoors.
NOTE - Flue gas may be slightly acidic and may adverse-
ly aect some building  materials. If any  vent termination 
is used and the ue gasses may impinge on the building 
material, a corrosion-resistant shield (minimum 24 inches 
square) should be used to protect the wall surface. If the 
optional tee is used, the protective shield is recommend-
ed. The shield should be constructed using wood, plastic, 
sheet metal  or  other  suitable  material. All  seams,  joints, 
cracks, etc. in the aected area should be sealed using an 
appropriate sealant. See FIGURE 37.
Intake and exhaust pipes may be routed either horizontal-
ly through an outside wall or vertically through the roof. In 
attic or closet installations, vertical termination through the 
roof is preferred. FIGURE 29 through FIGURE 36 shows 
typical terminations.
1 -   Vent terminations are not required to be in the same 
pressure zone. You may exit the intake on one side 
of  the  structure  and  the  exhaust  on  another  side 
(FIGURE 30). You may exit the exhaust out the roof 
and the intake out the side of the structure (FIGURE 
31).
2 -   Intake and exhaust pipes should be placed as close 
together  as  possible  at  termination  end  (refer  to 
illustrations).  Maximum  separation  is  3”  (76mm) 
on roof  terminations and  6”  (152mm) on  side wall 
terminations.
NOTE - When venting in dierent  pressure zones, 
the maximum separation requirement of intake and 
exhaust pipe DOES NOT apply.
3 -   On  roof  terminations,  the  intake  piping  should 
terminate straight down using two 90° elbows (See 
FIGURE 29).
4 -   Exhaust piping must terminate straight out or up as 
shown. A reducer may be required on the exhaust 
piping  at  the  point  where  it  exits  the  structure  to 
improve  the  velocity  of  exhaust  away  from  the 
intake piping. See TABLE 17.
5 -   On  eld-supplied  terminations  for  side  wall  exit, 
exhaus  piping may extend a maximum of 12 inches 
(305mm) for 2” PVC and 20 inches (508mm) for 3” 
(76mm) PVC beyond the outside wall. Intake piping 
should be as short as possible. See FIGURE 37.
NOTE - Care must be taken to avoid recirculation of 
exhaust back into intake pipe.
6 -   On eld supplied terminations, a minimum distance 
between the end of the exhaust pipe and the end of 
the intake pipe without a termination elbow is 8” and 
a minimum distance of 6” with a termination elbow. 
See FIGURE 37.
UNCONDITIONED
ATTIC SPACE
12” (305mm) ABOVE
AVERAGE SNOW
ACCUMULATION
3” (76mm) OR
2” (51mm) PVC
PROVIDE SUPPORT
FOR INTAKE AND
EXHAUST LINES
8” (203mm) MIN
Inches(mm)
DIRECT VENT ROOF TERMINATION KIT
FIGURE 29 
Exhaust
Pipe
Furnace
Exiting Exhaust and Intake Vent
(different pressure zone)
Inlet Air
(Minimum 12 in.
305 MM) above
grade or snow
accumulation
FIGURE 30 
Roof T
erminated
Exhaust Pipe
Furnace
Exiting Exhaust and Intake Vent
(different pressure zone)
Inlet Air
(Minimum 12 in.
305 MM) above
grade or snow
accumulation
FIGURE 31 
TABLE 17 
EXHAUST PIPE TERMINATION SIZE REDUCTION
ML296UHV Model Termination Pipe Size
*045 and 070 1-1/2” (38MM)
*090 2” (51MM)
110 2” (51MM)
*ML296UHV-045, -070 and -090 units with the ush mount termination 
must use the 1-1/2”accelerator supplied with the kit.