Page 45
NOTE- To obtain accurate reading, shut o all other gas 
appliances connected to meter.
TABLE 18 
GAS METER CLOCKING CHART
ML296
Unit
Seconds for One Revolution
Natural LP
1 cu ft 
Dial
2 cu ft 
Dial
1 cu ft 
Dial
2 cu ft 
Dial
-045 80 160 200 400
-070 55 110 136 272
-090 41 82 102 204
-110 33 66 82 164
Natural-1000 btu/cu ft LP-2500 btu/cu ft
 IMPORTANT
For safety, shut unit o and remove manometer as 
soon as an accurate reading has been obtained. 
Take care to replace pressure tap plug.
G- Proper Combustion
Furnace should operate minimum 15 minutes with correct 
manifold pressure and gas ow rate before checking com-
bustion. See  sections  E-  and F-.  Take  combustion  sam-
ple  beyond  the  ue  outlet. TABLE  19  shows  acceptable 
combustions. The maximum carbon monoxide reading 
should not exceed 100 ppm.
TABLE 19 
ML296
Model
CO
2
% For Nat CO
2
% For L.P
Low Fire High Fire Low Fire High Fire
045 5.4 - 6.4 7.5 - 8.5 6.4 - 7.4 8.8 - 9.8
070 5.3 - 6.3 7.4 - 8.4 6.3 - 7.3 8.7 - 9.7
090 5.8 - 6.8 7.6 - 8.6 6.8 - 7.8 8.9 - 9.9
110 6.1 - 7.1 8.0 - 9.0 7.1 - 8.1 9.3 - 10.3
The maximum carbon monoxide reading should not exceed 100ppm.
H- High Altitude
The  manifold  pressure,  gas  orice  and  pressure  switch 
may  require  adjustment  or  replacement  to  ensure  prop-
er  operation  at  higher  altitudes.  See  TABLE  20  for  gas 
conversion  and  pressure  switch  kits.  See  TABLE  21  for 
manifold pressures
TABLE 20 
LP/Propane Conversion Kit and Pressure Switch Requirements at Varying Altitudes
Unit
Natural to
LP/Propane
High Altitude 
Natural Burner 
Orice Kit
High Altitude LP/
Propane Burner 
Orice Kit
High Altitude Pressure Switch
0 - 7500 ft 7501 - 10,000 ft 7501 - 10,000 ft 4501 - 7500 ft 7501 - 10,000 ft
045
*11K51 73W37 *11K46
14A47 14A50
070 14A54 14A53
090 14A57 14A54
110 14A46 14A51
135 14A49 14A51
* Conversion requires installation of a gas valve manifold spring which is provided with the gas conversion kit. Pressure switch is factory 
set. No adjustment necessary. All models use the factory-installed pressure switch from 0-4500 feet (0-1370 m).
TABLE 21 
Manifold and Supply Line Pressure 0-10,000ft.
Unit Gas
Manifold Pressure in. wg. Supply Line 
Pressure in. w.g 
0 - 10,000 ft.
0 - 4500 ft 4501 - 5500 ft. 5501 - 6500 ft 6501 - 7500 ft 7501 - 10,000 ft
Low 
Fire
High 
Fire
Low 
Fire
High 
Fire
Low 
Fire
High 
Fire
Low 
Fire
High 
Fire
Low 
Fire
High 
Fire
Min Max
All 
Sizes
Natural 1.7 3.5 1.6 3.3 1.5 3.2 1.5 3.1 1.7 3.5 4.5 13.0
LP/ 
Propane
4.5 10.0 4.2 9.4 4.0 9.1 3.9 8.9 4.5 10.0 11.0 13.0
NOTE - A natural to L.P. propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit installation instruction 
for the conversion procedure.