EasyManuals Logo
Home>Lennox>Air Conditioner>MLA030S4M

Lennox MLA030S4M Service Manual

Lennox MLA030S4M
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #136 background imageLoading...
Page #136 background image
136
Error Code: F0
Description: Outdoorcompressorcurrentoverloadsensed
General Note: Iftheoutdoorcurrentexceedsthecurrentlimitvalue,theLEDwilldisplaythefailure.
Checkwhethertheinputcurrentofthepower
supplyshouldnotexceedmorethan12Afor18KBTU
units.
For30K,18.5A.
For36K,itis23A
Yes
CheckwhethertherefrigerantsystemisOK.
Checkwhethertheoutdoorambienttemperature
ishigherthan50°Cor122F
No
Replaceoutdoormainboard.
No
Stoptheunit.
Yes
Checkifoutdoorunithasproperventilation.
No
Correct poor ventilation to outdoor unit.
Yes
Checkoutdoorcoils.Outdoorcoilsshouldbeclean
and free of any debris.
Clean outdoor coils.
Yes
No
Judge5:Therefrigerantpipeisblocked.
Recoverrefrigerantandremoverestriction(s).
Performpropervacuumprocedures,then
restart system.
Yes
No
Replaceoutdoormainboard,andcheckwhetherthe
system can run normally.
No
Replacetheelectriccontrolbox.
Problem Solved.
Yes
Yes

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox MLA030S4M and is the answer not in the manual?

Lennox MLA030S4M Specifications

General IconGeneral
BrandLennox
ModelMLA030S4M
CategoryAir Conditioner
LanguageEnglish

Related product manuals