Page 33
Electrical
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
 CAUTION
Electrostatic discharge can aect electronic components. 
Take precautions during furnace installation and service 
to protect the furnace’s electronic controls. Precautions 
will help to avoid control exposure to electrostatic 
discharge by putting the furnace, the control and the 
technician at the same electrostatic potential. Neutralize 
electrostatic charge by touching hand and all tools on an 
unpainted unit surface, such as the gas valve or blower 
deck, before performing any service procedure.
 WARNING
Electric Shock Hazard. Can cause injury or 
death. Unit must be properly grounded in 
accordance with national and local codes.
 WARNING
Fire Hazard. Use of aluminum wire with this product may 
result in a re, causing property damage, severe injury 
or death. Use copper wire only with this product..
 CAUTION
Failure to use properly sized wiring and circuit breaker 
may result  in  property damage. Size  wiring  and circuit 
breaker(s) per Product Specications bulletin (EHB) and 
unit rating plate.
INTERIOR MAKE-UP BOX INSTALLATION
MAKE-UP
BOX
Right Side
FIGURE 51 
The unit is equipped with a eld make-up box on the left 
hand side of the cabinet. The make-up box may be moved 
to the right side of the furnace to facilitate installation. If 
the make-up box is moved to the right side, clip the wire 
ties that bundle the wires together. The excess wire must 
be pulled into the blower compartment. Secure the excess 
wire to the existing harness to protect it from damage.
See FIGURE 52 and FIGURE 53 for thermostat wiring in 
communicating applications. TABLE 15 shows DIP switch 
and on-board link settings for non-communicating ther-
mostat applications. Typical wiring schematic is shown in 
FIGURE 54.
1 -   The power supply wiring must meet Class I 
restrictions. Protected by either a fuse or circuit 
breaker,  select  circuit  protection  and  wire  size 
according to unit nameplate.
NOTE - Unit  nameplate  states  maximum  current  draw. 
See TABLE 12 for maximum over-current protection.
TABLE 12 
SL99UHV Model
Maximum Over-Current 
Protection Amps
070-36B, 090-36C, 090-48C 15
090-60C, 110-60C, 135-60D 20
2 -   Holes are on both sides of the furnace cabinet to 
facilitate wiring.
3 -   Install a separate (properly sized) disconnect switch 
near the furnace so that power can be turned o for 
servicing.
4 -   Before connecting the thermostat or the power 
wiring, check to make sure the wires will be long 
enough for servicing at a later date. Remove the 
blower access panel to check the length of the wire.
5 -   Complete the wiring connections to the equipment. 
Use the provided unit wiring and eld wiring diagram 
shown in FIGURE 54 and TABLE 15. Use 18-gauge 
wire or larger that is suitable for Class II rating for 
thermostat connections.
NOTE - Do NOT make a wire connection between 
the room thermostat L terminal and the L terminal 
of the SLP99UHV integrated control unless this 
is a communicating thermostat installation with 
a non-communicating outdoor unit.
6 -   Electrically ground the unit according to local codes 
or, in the absence of local codes, according to the 
current National Electric Code (ANSI/NFPA No. 70) 
for the USA and current Canadian Electric Code 
part 1 (CSA standard C22.1) for Canada. A green 
ground wire is provided in the eld make-up box.
7 -   One line voltage “EAC” 1/4” spade terminal is 
provided on the furnace integrated control. Any 
electronic air cleaner or other 120V accessory rated 
up to one amp can be connected to this terminal 
with the neutral leg