Page 57
2 -   Verify that system total static pressure and airow 
settings are within specic operating parameters.
3 -   Clock gas meter to ensure that the unit is operating 
at the specied ring rate for each stage of operation. 
Check supply, manifold and signal pressures at 
35, 70 and 100% capacity as outlined in the unit 
Service Literature. If manifold pressure adjustment 
is necessary, consult the Service Literature for unit 
specic  information  on  adjusting  gas  pressure. 
Not all gas valves are adjustable. Verify correct 
temperature rise.
NOTE - After any heavy snow, ice or frozen fog event the 
furnace vent pipes may become restricted. Always check 
the vent system and remove any snow or ice that may be 
obstructing the plastic intake or exhaust pipes.
Winterizing and Condensate Trap Care
1 -  Turn o power to the unit.
2 -    Have a shallow pan ready to empty condensate 
water.
3 -   Remove the drain plug from the condensate trap 
and empty water. Inspect the trap then reinstall the 
drain plug and rell trap with water.
Cleaning the Burner Assembly
1 -   Turn o electrical and gas power supplies to furnace. 
Remove upper and lower furnace access panels.
2 -  Disconnect the 2-pin plug from the gas valve.
3 -  Remove the burner box cover.
4 -   Disconnect the gas supply line from the gas valve. 
Remove gas valve/manifold assembly.
5 -   Mark and disconnect sensor wire from the sensor. 
Disconnect wires from ame rollout switches.
6 -   Remove four screws which secure burner box 
assembly to vest panel. Remove burner box from 
the unit. 
7 -   Use the soft brush attachment on a vacuum cleaner 
to gently clean the face of the burners. Visually 
inspect the inside of the burners and crossovers for 
any blockage caused by foreign matter. Remove 
any blockage.
8 -   Reinstall the burner box assembly using the existing 
four screws. Make sure that the burners line up in 
the center of the burner ports.
9 -   Reconnect the sensor wire and reconnect the 2-pin 
plug to the ignitor wiring harness. Reconnect wires 
to ame rollout switches.
10 -  Reinstall the gas valve manifold assembly. 
Reconnect the gas supply line to the gas valve. 
Reinstall the burner box cover.
11 - Reconnect 2-pin plug to gas valve.
12 - Replace the blower compartment access panel.
13 -  Refer to instruction on verifying gas and electrical 
connections when re-establishing supplies.
14 -  Follow lighting instructions to light and operate 
furnace for 5 minutes to ensure that heat exchanger 
is clean and dry and that furnace is operating 
properly.
15 - Replace heating compartment access panel.