Page 30
Gas Piping
 CAUTION
If a exible gas connector is required or allowed by the 
authority that has jurisdiction, black iron pipe shall be 
installed at the gas valve and extend outside the furnace 
cabinet.  The  exible  connector  can  then  be  added 
between the black iron pipe and the gas supply line.
 WARNING
Do not over torque (800 in-lbs) or under torque (350 in-
lbs) when attaching the gas piping to the gas valve.
1 -   Gas piping may be routed into the unit through either 
the left-or right-hand side in upow applications, and 
either  the  top  or  bottom  in  horizontal applications. 
Supply piping enters into the gas valve from the 
side of the valve as shown in FIGURE 49 and 
FIGURE 50. Connect the gas supply piping into the 
gas valve. The maximum torque is 800 in lbs and 
minimum torque is 350 in lbs when attaching the 
gas piping to the gas valve.
2 -   When connecting gas supply, factors such as length 
of  run,  number  of  ttings  and  furnace rating  must 
be considered to avoid excessive pressure drop. 
TABLE 11 lists recommended pipe sizes for typical 
applications.
NOTE - Use  two  wrenches  when  connecting  gas 
piping to avoid transferring torque to the manifold.
3 -   Gas piping must not run in or through air ducts, 
clothes chutes, chimneys or gas vents, dumb 
waiters or elevator shafts. Center gas line through 
piping hole. Gas line should not touch side of unit. 
See FIGURE 49 and FIGURE 50.
4 -   Piping should be sloped 1/4 inch per 15 feet (6mm 
per 5.6m) upward toward the gas meter from the 
furnace. The piping must be supported at proper 
intervals, every 8 to 10 feet (2.44 to 3.05m), using 
suitable hangers or straps. Install a drip leg in 
vertical pipe runs to serve as a trap for sediment or 
condensate.
5 -   A 1/8” N.P.T. plugged tap or pressure post is located 
on the gas valve to facilitate test gauge connection. 
See FIGURE 56.
6 -    In some localities, codes may require installation of 
a manual main shut-o valve and union (furnished 
by installer) external to the unit. Union must be of 
the ground joint type.
 IMPORTANT
Compounds used on threaded joints of gas piping must 
be resistant to the actions of liquied petroleum gases.
MANUAL MAIN SHUT-OFF
VALVE WILL NOT HOLD
NORMAL TEST PRESSURE
CAP
FURNACE
ISOLATE
GAS VALVE
1/8” N.P. T. PLUGGED TAP
FIGURE 48 
Leak Check
After gas piping is completed, carefully check all eld-in-
stalled piping connections for gas leaks. Use a commer-
cially available leak detecting solution specically manu-
factured for leak detection. Never use an open ame to 
test for gas leaks.
The  furnace  must  be  isolated  from  the  gas  supply  sys-
tem by closing the individual manual shut-o valve during 
any gas supply system at pressures greater than or equal 
to  ½  psig.  (3.48  kPa,  14  inches  w.c.).  This  furnace  and 
its  components  are  designed,  manufactured  and  inde-
pendently certied to comply with all applicable ANSI/CSA 
standards. A leak check of the furnace and its components 
is not required. 
 IMPORTANT
When testing gas lines using pressures in excess of 1/2 
psig (3.48 kPa), gas valve must be disconnected and 
isolated. See FIGURE 48. Gas valves can be damaged 
if subjected to pressures greater than 1/2 psig (3.48 
kPa)..
 WARNING
FIRE OR EXPLOSION HAZARD..
Failure to follow the safety warnings exactly could result 
in serious injury, death, or property damage. Never use 
an open ame to test for gas leaks. Check all connections 
using a commercially available soap solution made 
specically for leak detection. Some soaps used for leak 
detection are corrosive to certain metals. Carefully rinse 
piping thoroughly after leak test has been completed.