Page 54
Pressure Switches (Two)
The pressure switches are located on the cold end header 
box. These switches check for proper combustion air in-
ducer operation before allowing ignition trial. The switch-
es are factory-set and require no adjustment. Pressure 
switch tubing installation is critical for safe operation. See 
FIGURE 59.
PRESSURE SWITCH TUBING INSTALLATION
(shown in upflow position)
Gas Valve
Cold End Header Box
High-Fire
Pressure Switch
Low-Fire
Pressure Switch
1
2
3
4
1 -  Black tubing from front port on low-fire pressure switch to
positive port on the gas valve.
2 -  Red and black tubing from rear port on low-fire pressure
switch to the negative port on the gas valve.
3 -  Red and black tubing from front port on high-fire pressure
switch to negative port on cold end header box.
4 -  Black tubing from rear port on high-fire pressure switch to
positive port on cold end header box.
FIGURE 59 
Temperature Rise
After the furnace has been started and supply and return 
air  temperatures  have  been  allowed  to  stabilize,  check 
the temperature rise with the unit operating at 100 per-
cent  ring  rate.  See  “Duct  System”  on  page  10  for  in-
stalling the optional discharge air sensor (shipped with the 
furnace) used to measure temperature rise. If necessary, 
adjust the blower speed to maintain the temperature rise 
within the range shown on the unit nameplate. See TABLE 
24 on page 48 for allowable heating speeds.Increase 
the blower speed to decrease the temperature. Decrease 
the blower speed to increase the temperature rise. Failure 
to adjust the temperature rise may cause erratic limit op-
eration.
Electronic Ignition
The integrated control has an added feature of an inter-
nal Watchguard control. The feature serves as an auto-
matic reset device for ignition control lockout caused by 
ignition failure. This type of lockout is usually due to low 
gas line pressure. After one hour of continuous thermostat 
demand for heat, the Watchguard will break and remake 
thermostat demand to the furnace and automatically reset 
the control to begin the ignition sequence.
Exhaust and Air Intake Pipe
1 -   Check exhaust and air intake connections for 
tightness and to make sure there is no blockage.
2 -   Are pressure switches closed? Obstructed exhaust 
pipe will cause unit to shut o at pressure switches. 
Check termination for blockages.
3 -   Reset manual ame rollout switches on burner box 
cover.
Heating Sequence of Operation
The integrated control initiates a pressure switch calibra-
tion at the initial unit start-up on a call for heat. The ignition 
control will also initiate a calibration any time main power 
is turned o and back on and a heating demand is pres-
ent . Additional calibrations may be initiated by the ser-
vice technician  during eld test  sequence. The following 
heating sequence of operation assumes completion of a 
successful calibration.
NOTE - In communicating applications, the sequence of 
operation is the same but all DIP switch settings are ove-
ridden by the thermostat.
NOTE - The thermostat selection DIP switch on the inte-
grated control is factory-set in the “TWO-STAGE” position.
Applications Using a Two-Stage Thermostat
A - Heating Sequence -- Control Thermostat Selection
DIP switch in “Two-Stage” Position (Factory Setting)
1 -   On  a  call  for  heat,  thermostat  rst-stage  contacts 
close sending a signal to the integrated control. The 
integrated control runs a self-diagnostic program 
and checks high temperature limit switches for 
normally closed contacts and pressure switches 
for normally open contacts. The combustion air 
inducer  is  energized  at  ignition  speed,  which  is 
approximately the same as the inducer speed at 70 
percent ring rate.
2 -   Once the control receives a signal that the low-
re  pressure  switch  has  closed,  the  combustion 
air inducer begins a 15-second pre-purge in the 
ignition speed.
3 -   After the pre-purge is complete, a 20-second initial 
ignitor warm-up period begins. The combustion air 
inducer continues to operate at the ignition speed.
4 -   After the 20-second warm-up period has ended, 
the  gas  valve  is  energized  and  ignition occurs. At 
the same time, the control module sends a signal to 
begin an indoor blower 30-second ON-delay. When 
the delay ends, the indoor blower motor is energized 
at  a  speed  that  matches  the  ring  rate.  After  the 
10-second  ignition  stabilization  delay  expires,  the