Applications Using A Single-Stage Thermostat
See gure 37 for ignition control sequence
B - Heating Sequence -- Integrated Control Thermostat
Selection DIP Switch 1 ON in “Single-Stage” Position
NOTE - In these applications, two-stage heat will be initiat-
ed by the integrated control if heating demand has not been
satised after the eld adjustable period (7 or 12 minutes).
1 - On a call for heat, thermostat rst-stage contacts
close sending a signal to the integrated control. The
integrated control runs a self-diagnostic program
and checks high temperature limit switches for
normally closed contacts and pressure switches for
normally open contacts. The combustion air inducer is
energized at low speed.
2 - Once the control receives a signal that the low pressure
switch has closed, the combustion air inducer begins
a 15-second pre-purge in low speed
NOTE - If the low re pressure switch does not close
the combustion air inducer will switch to high re.
After a 15 second pre-purge the high re pressure
switch will close and the unit will begin operation on
high re. After 10 to 20 seconds of high re operation
the unit will switch to low re.
3 - After the pre-purge is complete, a 20-second initial
ignitor warm-up period begins. The combustion air
inducer continues to operate at low speed
4 - After the 20-second warm-up period has ended, the
gas valve is energized on low re (rst stage) and
ignition occurs. At the same time, the control module
sends a signal to begin an indoor blower 30-second
ON-delay. When the delay ends, the indoor blower
motor is energized on the low re heating speed
and the HUM contacts are energized. The integrated
control also initiates a second-stage on delay (factory-
set at 7 minutes; adjustable to 12 minutes).
5 - If the heating demand continues beyond the
secondstage on delay, the integrated control
energizes the combustion air inducer at high speed.
The control also checks the high re (second stage)
pressure switch to make sure it is closed. The high re
(second stage) gas valve is energized and the indoor
blower motor is energized for operation at the high re
heating speed.
6 - When the thermostat heating demand is satised, the
combustion air inducer begins a 5-second low speed
post-purge. The eld-selected indoor blower off delay
begins. The indoor blower operates at the low-re
heating speed.
7 - When the combustion air post-purge period is
complete, the inducer, the HUM contacts as well as
the 120V ACC terminals are de-energized. The indoor
blower is de-energized at the end of the off delay.
FIGURE 36
FIGURE 37
1 stg heat demand
2 stg heat demand
15
ON
OFF
low speed CAI
35
1
Pre-Purge
Ignitor Warm-up
30* second
blower
“on” delay
Post
Purge
5 SEC80
ignitor
HEATING OPERATION WITH TWO-STAGE THERMOSTAT
low fire gas valve
indoor blower low heat
high speed CAI
high fire gas valve
indoor blower high heat
39
Trial For
Ignition
blower
“off”
delay
RECOGNITION PERIOD
30 seconds
* Conventional thermostat 30 seconds, icomfort Touch
®
thermostat set for 30 adjustable 15 to 45 seconds.
heat demand
15
ON
OFF
low speed CAI
35
1
Pre-Purge
Ignitor Warm-up
30* second
blower
“on” delay
Post
Purge
5 SEC
80
ignitor
HEATING OPERATION WITH SINGLE STAGE THERMOSTAT
low fire gas valve
high speed CAI
high fire gas valve
indoor blower high heat
39
Trial For
Ignition
7 or 12 minutes after heating demand begins, furnace switches to high fire (depends on setting)
blowe
r
“off”
delay
indoor blower low heat
* Conventional thermostat 30 seconds, icomfort Touch
®
thermostat set for 30 adjustable 15 to 45 seconds.

Other manuals for Lennox SL280DF070V36A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox SL280DF070V36A and is the answer not in the manual?

Lennox SL280DF070V36A Specifications

General IconGeneral
BrandLennox
ModelSL280DF070V36A
CategoryFurnace
LanguageEnglish

Related product manuals