Page 40
TABLE 22
Maximum Allowable Exhaust Vent Lengths With Furnace Installed in a
Closet or Basement Using VentilatedAttic or Crawl Space For Intake Air in Feet
NOTE - Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake
and Exhaust must be same pipe size.
NOTE - Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent length
calculation
.
Standard Termination at Elevation 0 - 4500 ft
Number Of 90°
Elbows Used
2” Pipe 3” Pipe
Model Model
040 060 080 040 060 080
1 71    117 
2   29  112 
  24  107 
4  41 19  102 
  14  97 
  9  92 
7 41  4   
 21

  
9    77 
10  11  72 
Standard Termination at Elevation 4501 - 6000 ft
Number Of 90°
Elbows Used
2” Pipe 3” Pipe
Model Model
040 060 080 040 060 080
1 71  24   
2   19   
 21 14   70
4   9  70 
 11

  


  
7 41   
   
9    40
10   40 
Standard Termination at Elevation 6001 - 7500 ft
Number Of 90°
Elbows Used
2” Pipe 3” Pipe
Model Model
040 060 080 040 060 080
1 71 19 14   
2  14 9   
 9

  70
4 

 70 
   
   
7 41   
   
9    40
10   40 