TABLE 24 
OPERATING SEQUENCE 
SLP98DFV and Two-Speed Outdoor Unit
OPERATING 
SEQUENCE
SYSTEM DEMAND SYSTEM RESPONSE
System
Condition
Step
Thermostat Demand Relative Humidity
Compressor
Blower 
CFM 
(cool)
Comments
1st 
stage 
2nd
stage
O G Status D*
NO CALL FOR DEHUMIDIFICATION
Normal Operation 
Y1
1 On On On Acceptable
24 
VAC
Low 70%
Compressor and indoor blower 
follow thermostat demand
Normal Operation 
Y2
2 On On On On Acceptable
24 
VAC
High 100%
ROOM THERMOSTAT CALLS FOR FIRST STAGE COOLING
BASIC MODE (only active on a Y1 thermostat demand)
Normal Operation 1 On On On Acceptable
24 
VAC
Low 70%
Thermostat energizes 2nd stage 
and de-energizes D on a call for 
dehumidication
Dehumidication 
call
2 On On On On Demand
0 
VAC
High 70%
PRECISION MODE (operates independent of a Y1 demand)
Normal Operation 1 On On On Acceptable
24 
VAC
Low 70%
Dehumidication mode begins 
when humidity is greater than 
set point
Dehumidication 
Call
2 On On On On Demand
0 
VAC
High 70%
Dehumidication 
Call Only
1 On On On On Demand
0 
VAC
High 70%
Thermostat will keep outdoor 
unit energized after cooling 
temperature setpoint has been 
reached in order to maintain 
room humidity setpoint.*
ROOM THERMOSTAT CALLS FOR FIRST AND SECOND STAGE COOLING
BASIC MODE (only active on a Y1 thermostat demand)
Normal Operation 1 On On On On Acceptable
24 
VAC
High 100%
Thermostat energizes 2nd stage 
and de-energizes D on a call for 
dehumidication
Dehumidication 
Call
2 On On On On Demand
0 
VAC
High 70%
PRECISION MODE (operates independent of a Y1 thermostat demand)
Normal Operation 1 On On On Acceptable
24 
VAC
Low 70%
Dehumidication mode begins 
when humidity is greater than 
set point
Dehumidication 
Call
2 On On On On Demand
0 
VAC
High 70%
Dehumidication 
Call ONLY
1 On On On On Demand
0 
VAC
High 70%
Thermostat will keep outdoor 
unit energized after cooling 
temperature set-point has been 
reached in order to maintain 
room humidity set-point.
On-board links at indoor unit with a two-stage outdoor unit:
Cut factory link from Y1 to Y2 or cut W915 (Y1 to Y2) on SureLight® integrated control.
With Condensing unit - Cut W914 (R to DS) on SureLight® integrated control;
With Heat Pump - Cut W914 (R to DS) & W951 (R to O) on SureLight® integrated control.
*ComfortSense® 7500 thermostat only