Page 9
COOLING COIL
PLENUM
PROPERLY
SIZED FLOOR
OPENING
FURNACE
FIGURE 10 
Return Air Opening -- Downow Units
Return air may be brought in only through the top opening 
of a furnace installed in the downow position. The follow-
ing steps should be taken when installing plenum:
1 -   Bottom  edge  of  plenum  should  be  anged  with  a 
hemmed edge (See gure 11 or 12).
2 -   Sealing strips should be used to ensure an airtight 
seal between the cabinet and the plenum.
3 -   In all cases, plenum should be secured to top of 
furnace using sheet metal screws.
4 -  Make certain that an adequate seal is made.
SECURE FROM
OUTSIDE CABINET
PLENUM
(Field Provided)
SEALING STRIP
(Field Provided)
Side View
CABINET
SIDE PANEL
FIGURE 11 
SECURE FROM
INSIDE CABINET
PLENUM
(Field Provided)
SEALING STRIP
(Field Provided)
Side View
CABINET
SIDE PANEL
FIGURE 12 
Filters
This unit is not equipped with a lter or rack. A eld-provid-
ed lter is required for the unit to operate properly. Table 3 
lists recommended lter size.
A lter must be in place whenever the unit is operating.
 IMPORTANT
If a highefciency lter is being installed as part of this 
system to ensure better indoor air quality, the lter must 
be  properly  sized.  Highefciency  lters  have  a  higher 
static pressure drop than standardefciency glass/foam 
lters. If the pressure drop is too great, system capacity 
and performance may be reduced. The pressure drop 
may also cause the limit to trip more frequently during 
the winter and the indoor coil to freeze in the summer, 
resulting in an increase in the number of service calls.
Before  using  any  lter  with  this  system,  check  the 
specications provided by the lter manufacturer against 
the data given in the appropriate Lennox Product 
Specications bulletin. Additional information is provided 
in Service and Application Note ACC002 (August 2000).
TABLE 3
Furnace Cabinet Width Fillter Size
B Cabinet 17-1/2”
16 X 25 X 1 (1)
C Cabinet 21-1/2”
Duct System
Use  industry-approved  standards  to  size  and  install  the 
supply and return air duct system. This will result in a quiet 
and low-static system that has uniform air distribution.
NOTE - Operation of this furnace in heating mode (indoor 
blower operating  at  selected heating  speed)  with an  ex-
ternal static pressure which exceeds 0.8 inches w.c. may 
result in erratic limit operation.
Return Air Plenum
Return air must not be drawn from a room where this 
furnace, or any other gas-fueled appliance (i.e., water 
heater), or carbon monoxide-producing device (i.e., 
wood  replace)  is  installed.  When return air is drawn 
from a room, a negative pressure is created in the room. If 
a gas appliance is operating in a room with negative pres-
sure, the ue products can be pulled back down the vent 
pipe and into the room. This reverse ow of the ue gas 
may result in incomplete combustion and the formation of 
carbon monoxide gas. This toxic gas might then be dis-
tributed throughout the house by the furnace duct system.
Use berglass sealing strips, caulking, or equivalent seal-
ing method between the plenum and the furnace cabinet 
to ensure a tight seal. If a lter is installed, size the return 
air duct to t the lter frame.