Page 7
NOTE - The  1/2  hp  blower  motor  used  in  the  SLP98D-
F070V36B  and  SLP98DF090V36C  unit  is  equipped 
with  three  exible  legs  and  one  rigid  leg.  The  rigid  leg 
is  equipped  with  a  shipping  bolt  and  a  at  white  plastic 
washer  (rather than the rubber  mounting  grommet  used 
with a exible mounting leg). The bolt and washer must 
be removed before the furnace is placed into opera-
tion. After the bolt and washer have been removed, the 
rigid leg will not touch the blower housing.
RIGID LEG
remove shipping bolt and washe
UNITS  WITH 1/2 HP
BLOWER MOTOR
FIGURE 6 
Allow for clearances to combustible materials as indicated 
on the unit nameplate. Minimum clearances for closet or 
alcove installations are shown in gure 7.
 WARNING
The blower access panel must be securely in place when 
the blower and burners are operating. Gas fumes, which 
could contain carbon monoxide, can be drawn into living 
space resulting in personal injury or death.
 WARNING
Improper installation of the furnace can result in personal 
injury  or  death.  Combustion  and  ue  products  must 
never be allowed to enter the return air system or air in 
the living space. Use sheet metal screws and joint tape 
to seal return air system to furnace.
In platform installations with furnace return, the furnace 
should be sealed airtight to the return air plenum. A door 
must never be used as a portion of the  return air duct 
system. The base must provide a stable support and an 
airtight seal to the furnace. Allow absolutely no sagging, 
cracks, gaps, etc. For no reason should return and 
supply air duct systems ever be connected to or from 
other heating devices such as a replace or stove, etc. 
Fire, explosion, carbon monoxide poisoning, personal 
injury and/or property damage could result.
IThe unit may be installed three ways in downow applica-
tions: on non-combustible  ooring, on  combustible oor-
ing using a base, or on a reverse-ow cooling coil cabinet. 
Do not drag the unit across the oor in the downow 
position. Floor and ange damage will result. Refer to 
gure 7 for clearances in downow applications.
Downflow Application Installation Clearances
Top
Bottom
Left Side Right Side
Top 0
*Front 0
Back 0
Sides 0†
Vent 0
Floor NC‡
*Front clearance in alcove installation must be 24 in. (610 mm).
Maintain a minimum of 24 in. (610 mm) for front service access.
†Allow proper clearances to accommodate condensate trap and
vent pipe installation.
‡
tional base is installed between the furnace and the combustible
floor.
FIGURE 7 
Installation on Non-Combustible Flooring (Figure 8)
1 -   Cut oor opening keeping in mind clearances listed 
on unit rating plate. Also keep in mind gas supply 
connections,  electrical  supply,  ue  and  air  intake 
connections and sufcient installation and servicing 
clearances.  See  table  1  for  correct  oor  opening 
size.
2 -   Flange warm air plenum and lower the plenum into 
the opening.
3 -   Set the unit over the plenum and seal the plenum 
to the unit.
Ensure that the seal is adequate.