5
Material type
Total length of
communication line
between indoor unit and
wired controller L (m/feet)
Wire size
(mm
2
/AWG)
Material
Standard
Remarks
Light/Ordinary
polyvinyl
chloride
sheathed cord.
(60227 IEC 52
/60227 IEC 53)
L
250m
(L
820-1/5feet)
0.75~2×1.25
(2×AWG18~2×AW
G16)
IEC
60227-5:200
7
1.Total length of communication line
can't exceed 250m (820-1/5feet).
2.The cord shall be Circular cord (the
cores shall be twisted together).
3.If unit is installed in places with intense
magnetic field or strong interference, it is
necessary to use shielded wire.
3.3.2 Select communication line for indoor unit and indoor unit (outdoor unit)
Fig 3.3.2
Material Type
Total Length L (m/feet)
of Communication
Cable between Indoor
Unit and Indoor
(Outdoor) Unit
Wire size
(mm
2
/AWG)
Material
Standard
Remarks
Light/Ordinary
polyvinyl
chloride
sheathed cord.
(60227 IEC 52
/60227 IEC 53)
L
1000m
(L
3280-5/6feet)
0.75
(
AWG18)
IEC
60227-5:2007
1. If the wire diameter is enlarged to 2×1
mm
2
(AWG16), the total
communication line length can reach
1500 m (4921-1/4feet).
2. The cord shall be Circular cord (the
cores shall be twisted together).
3. If unit is installed in places with
intense magnetic field or strong
interference, it is necessary to use
shielded wire.
3.4 Wiring Requirements
Model Power Cord Size
Air Switch
apacity
(A)
Minimum Sectional
Area of
Ground Wire(mm
2
)
Minimum Sectional
Area of Power
Cord(mm
2
)
VEHW007N432T
VEHW009N432T
VEHW012N432T
VEHW015N432T
VEHW017N432T
VEHW019N432T
VEHW021N432T
VEHW024N432T
220-240V ~ 50Hz
6
1
1
High Wall Type Indoor Unit

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox VEHW007N432T and is the answer not in the manual?

Lennox VEHW007N432T Specifications

General IconGeneral
BrandLennox
ModelVEHW007N432T
CategoryAir Conditioner
LanguageEnglish

Related product manuals