XP16
TEST
Placing the jumper on the field test pins (E33) allows the technician to:
D Clear short cycle lockout
D Clear five−strike fault lockout
D Cycle the unit in and out of defrost mode
D Place the unit in defrost mode to clear the coil
When Y1 is energized and 24V power is being applied to the Control, a test cycle can be initiated by placing a jumper on the Control’s TEST pins for 2
to 5 seconds. If the jumper remains on the TEST pins for longer than five seconds, the Control will ignore the jumpered TEST pins and revert to
normal operation.
The Control will initiate one test event each time a jumper is placed on the TEST pins. For each TEST the jumper must be removed for at least
one second and then reapplied.
NOTE  Placing a jumper on the TEST pins will not bring the
unit out of inactive mode. The only way manually activate the
heat pump from an inactive mode is to cycle the 24VAC power
to the Control.
Y1 Active
Place a jumper on TEST pins for
longer than one second but less
than two seconds.
Clears any short cycle lockout and
five strike fault lockout function, if
applicable. No other functions will
be executed and unit will continue in
the mode it was operating.
Place a jumper on TEST pins for
more than two seconds.
Clears any short cycle lockout and
five strike fault lockout function, if
applicable.
If in HEATING Mode
If in DEFROST Mode
No further test mode operation will
be executed until the jumper is
removed from the TEST pins and
reapplied.
If no ambient or coil sensor fault
exist, unit will go into DEFROST
MODE.
If ambient or coil faults exist (open
or shorted), unit will remain in
HEAT MODE.
The unit will terminate defrost and
enter HEAT MODE uncalibrated
with defrost timer set for 34 minute
test.
If jumper on TEST pins remains in
place for more than five seconds.
The unit will return to HEAT MODE
uncalibrated with defrost timer set
for 34 minutes.
If jumper on TEST pins is removed
before a maximum of five seconds.
The unit will remain in DEFROST
MODE until termination on time or
temperature.
O Line Status
INACTIVE
ACTIVE
If in COOLING Mode
Figure 23. Test Mode