Severity: Warning
User Action:
Complete the following steps:
1. Check Lenovo support site for an applicable service bulletin or UEFI firmware update that applies to
this error.
2. A/C cycle the system.
3. If the problem persists, collect Service Data logs.
4. Contact Lenovo Support.
Service Action:
Complete the following steps:
1. Verify network between system and SKLM server.
2. Verify FoD key.
3. Verify SKLM configuration.
4. If problem persists, escalate to next level support.
• FQXSFIO0005I: An intra-board UPI has been disabled on the link between processor [arg1] port
[arg2] and processor [arg3]port [arg4] because of UPI topology downgrade.
Severity: Info
User Action:
Complete the following steps:
1. This event should be followed by a recent FQXSFIO0005M / FQXSFIO0006M event denoting some
UPI links failure which caused UPI topology downgrade.
2. Solve the event FQXSFIO0005M / FQXSFIO0006M at first, then this event should be solved
automatically.
3. If no recent or after fixing FQXSFIO0005M / FQXSFIO0006M event, this event still persists, collect
Service Data logs.
4. Contact Lenovo Support.
Service Action:
Information only; no action is required.
• FQXSFIO0005M: An intra-board UPI failure has been detected on the link between processor [arg1]
port [arg2] and processor [arg3] port [arg4].
Severity: Error
User Action:
Complete the following steps:
1. Check Lenovo support site for an applicable service bulletin or firmware update that applies to this
error.
2. If the problem persists, collect Service Data logs.
3. Contact Lenovo Support.
192
ThinkSystem SR850 V2 System Events Service Guide