Function library
Parameter set management
7−92
L
EDB82MV752 EN 5.2
Code IMPORTANTPossible settings
No. SelectionLenzeName
C0002*
uSEr
(cont.)
Parameter set
transfer using the
keypad
Keypad ð PAR1 (+ FPAR1)
Overwrite selected parameter set and, if
necessary, FPAR1 with the corresponding
keypad data
71 With function module Application−I/O, INTERBUS,
PROFIBUS−DP, LECOM−B, DeviceNet/CANopen
11 With all other function modules
Keypad ð PAR2 (+ FPAR1)
72 With function module Application−I/O, INTERBUS,
PROFIBUS−DP, LECOM−B, DeviceNet/CANopen
12 With all other function modules
Keypad ð PAR3 (+ FPAR1)
73 With function module Application−I/O, INTERBUS,
PROFIBUS−DP, LECOM−B, DeviceNet/CANopen
13 With all other function modules
Keypad ð PAR4 (+ FPAR1)
74 With function module Application−I/O, INTERBUS,
PROFIBUS−DP, LECOM−B, DeviceNet/CANopen
14 With all other function modules
Controller ð Keypad
All available parameter sets (PAR1 ... PAR4,
and FPAR1) are copied to the keypad
80 With function module Application−I/O, INTERBUS,
PROFIBUS−DP, LECOM−B, DeviceNet/CANopen
20 With all other function modules
Keypad ð Function module
Overwrite the module−specific parameter
set FPAR1 only
40 Only with function module INTERBUS,
PROFIBUS−DP, LECOM−B, DeviceNet/CANopen
Function module ð Keypad
Copy the module−specific parameter set
FPAR1 only
50 Only with function module INTERBUS,
PROFIBUS−DP, LECOM−B, DeviceNet/CANopen
C0002*
uSEr
(cont.)
Saving of own
settings
9 PAR1 ð Own settings You can save your own basic settings for a
controller (e.g. machine delivery status):
1. Ensure that parameter set 1 is active
2. Controller inhibit
3. Set C0003 = 3, acknowledge with
4. Set C0002 = 9, acknowledge with ,
to save your own basic settings
5. Set C0003 = 1, acknowledge with
6. Enable the controller.
C0002*
uSEr
(cont.)
Loading/copying of
your own basic
settings
Using this function, PAR1 can be copied to
parameter sets PAR2 ... PAR4
5 Own settings ð PAR1
Restorage of own basic setting in the
selected parameter set
6 Own settings ð PAR2
7 Own settings ð PAR3
8 Own settings ð PAR4
C0003*
Non−volatile
parameter saving
1
0 Parameter not saved in EEPROM Data loss after mains disconnection
1 Parameter always saved in EEPROM Active after every mains connection
Cyclic parameter changes via bus
module are not allowed.
3 Own settings saved in EEPROM Subsequently save parameter set 1 as own
basic setting with C0002 = 9