Appendix
Code table
14
404
EDBCSXA064 EN 3.2
IMPORTANTPossible settingsCode
SelectionLenze/
{Appl.}
DesignationNo.
[C0370] SDO gateway 0
Activate address
gateway/remote
parameterisation
The SDO gateway cannot be
used to read out codes >C2000
or codes of the Inverter Drives
8400 and Servo Drives 9400.
l C0370 ¹ 0: All code
write/read accesses are
redirected to the CAN node
with the CAN node address
set here.
l The corresponding code is
accessed via parameter data
channel 1 of the target device.
l C0370 = 0: remote
parameterisation is
deactivated
180
0 {1} 63
C0371 Gateway Ch. 1
Selection of the gateway channel
180
0 CAN Use CAN bus interface X4
1 CAN−AUX Use CAN bus interface X14
C0381 HeartProdTim
e
0
Heartbeat (slave):
HeartbeatProducerTime
l Time interval for sending the
heartbeat message
l Only relevant for setting
C0352 = 3.
0 {1 ms} 65535
C0382 GuardTime 0
Node Guarding (slave):
NodeGuardTime
l Time interval of the status
inquiry of the master
l Only relevant for setting
C0352 = 4.
172
0 {1 ms} 65535
C0383 LifeTimeFact 0
Node Guarding (slave):
NodeLifeTime factor
l Factor for the monitoring
time of NodeLifeTime
l NodeLifeTime = C0383 x
C0382 (NodeGuardTime)
l Only relevant for setting
C0352 = 4.
172
0 {1} 255
C0384 Err
NodeGuard
3
Node Guarding (slave)
l Response for the occurrence
of a NodeGuard−Event
l Only relevant for setting
C0352 = 4.
172
0 TRIP
1 Message
2 Warning
3 Off
4 FAIL−QSP