EasyManua.ls Logo

Lenze EL 110 PLC - Establish Communication: Bus Configurator Activation and Diagnostics

Lenze EL 110 PLC
84 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operation
Communicating via the CAN gateway function
Establishing communication using the system bus configurator
8
71
LDCDS−EL100 EN 8.0
Activating and diagnosing communication
Note!
Communication via the Global Drive Control (GDC) or the L−force Engineer only
works if the EL1xx has been defined as the standard device.
5. Right−click the communication module and select Activate from the context menu
to activate communication.
An activated device is indicated by a red check mark in the "active/default" column.
6. Define the EL1xx communication module as the standard device by another
right−click on the communication module in the system bus configurator and
selecting Default from the context menu.
The standard device is indicated by a black check mark in the "active/default" column.
EL100−038
7. Select the new module in the system bus configurator.
8. For communication diagnostics, open the "Common" tab and click the
Communication diagnostics button.
A message is displayed. Please observe the note contained therein saying that wrong
settings may lead to a bus switch−off and that Lenze will not accept any responsibility
or liability for damage which might possibly occur.
EL100−039

Table of Contents