Commissioning
820XBA1097 5-1
5 Commissioning
The controllers are factory-set to drive a corresponding four-pole
standard motor with 230/400V, 50Hz. Further settings are not
necessary.
Only afew settings via the8201 BB operating module or a fieldbus
module are necessary to adapt your drive to your application. The
steps required are summarized in chapter 5.3 and in chapter 5.4.
5.1 Before you switch on
Prior to initial switch-on of the controller, check the wiring for
completeness, short-circuit, and earth fault:
-
Power connection:
- Via terminals L1/N - 820X.
- Alternatively via terminals +UG, -UG (DC-group drive)
-
Control terminals:
- Reference potential for the control terminals is terminal 39.
- Controller enable: terminal 28
- Selection of direction of rotation: terminal E3 or E4
- External setpoint selection: terminals 8, 9
- Check jumper position! Factpr settomg: 0 - 10 V
(see page 4-10).
- During operation with an internal voltage supply via terminal
20, bride the terminals 7 and 39.