Function block library
7-208

SHB9300CRV EN 2.0
l
In factory setting, SPCx-L-IN is connected with the actual position value (POS-ACTPOS)of
the FB POS.
– Thus the switch points refer to the distance passed by the motor.
Assignment of switch-on and switch-off positions for SPC1 (see Fig. 7-166):
Code Subcode Switch point Output FB
C1641
1 IN1-1
SPC1-STAT1
2 IN1-2
... ... ... ...
C1641
15 IN8-1
SPC1-STAT8
16 IN8-2
Assignment of switch-on and switch-off positions for SPC2 (see Fig. 7-167):
Code Subcode Switch point Output FB
C1651
1 IN1-1
SPC2-STAT1
2 IN1-2
... ... ... ...
C1651
15 IN8-1
SPC2-STAT8
16 IN8-2
Mode 1: Start and end position
C1645 = set 0 (SPC1)
C1655 = set 0 (SPC2)
SPx-L-IN
SPx-L-IN
SPx-L-IN
Px-STAT1
Px-STAT2
Px-STAT8
IN1-1 IN1-2
IN2-1 IN2-2
IN8-1 IN8-2
HIGH
LOW
HIGH
LOW
HIGH
LOW
Fig. 7-168 Switch-on and switch-off positions for SPCx-STAT1, SPCx-STAT2 and SPCx-STAT8
Switch-on and switch-off positions depend on the travel direction:
SPx-STATx
SPx-L-IN
IN x -1
HIGH
LO W
IN x -2
Travel direction
(O N ) (O F F )
Fig. 7-169 Definition of a switc h-on and switch- off posit ion according t o the travel direction
Mode 2: Center with switch range
C1645 = set 1 (SPC1)
C1655 = set 1 (SPC2)