Function library
Function blocks
3.5.29 Digital frequency ramp function generator (DFRFG)
3−175
l
EDSVS9332P−EXT DE 2.0
3.5.29.6 Start via touch probe initiator (terminal X5/E5)
Stop!
In the default setting the terminal X5/E5 is assigned to another function.
Function
l Set C0757 = 1.
l The function is activated by simultaneously setting the inputs:
DFRFG−QSP and DFRFG−RESET = HIGH.
l Starting procedure:
Signals at DFRFG−QSP and DFRFG−RESET = LOW.
Otherwise touch probe signals are ignored.
l A LOW−HIGH edge at terminal X5/E5 starts the process:
t
DFRFG-RESET
DFRFG-QSP
Touch-Probe X5/E5
DFRFG-OUT
DFRFG-IN
Fig. 3−128 Start via touch probe initiator (terminal X5/E5)