Advanced sengs
Parameter Value Comment
Designaon Delivery Seng range
V
min
boost 0.0 % [0.0 ... 100.0] % Eecve only if Energy saving funcon = On:
•
Boost of the motor voltage in the range of low speeds.
•
In the case of conveyor applicaons with an inclined pro-
poron, a turn-back during start-up can be prevented.
•
Typical values approx. < 5 %.
I
max
in motor mode Device-dependent [0.00 ... Imax] A Maximum motor current
MSEMAxx063-42: 5.6 A
MSEMAxx080-32: 13.2 A
With a gearbox, the seng range can be smaller.
Reducing the I
max
causes a lower maximum torque.
Drives coupled mechanically No No, yes Reducing compensaon processes in case of heavy and long
conveyed loads which occupy several conveying elements at
the same me.
From rmware version 03.00.00.00
Motor overload seng (I
2
xt)
100.00 % [0.00 ... 250.00] % Limit value for motor overload cut‐o.
Recommended seng: 100 %
Starng value for motor over-
load (I
2
xt)
50.00 % [0.00 ... 100.00] % Recommended seng for operaon according to UL:
50.00 %
Motor brake switching
threshold
100 rpm [0 ... 499.9/i] rpm Motor brake is switched if the value is exceeded or is too
low.
Higher value: In the case of conveyor applicaons with an
inclined proporon, a turn-back during start-up can be pre-
vented.
Brake resistor R - ohms [150.0 ... 500.0]
ohms
Enter data of a connected brake resistor correctly.
If ed in the factory:
•
If an internal brake resistor is used, the values of the
brake resistor are preset.
•
If an external brake resistor is used, the values of the
brake resistor are preset. Only the rated power can be
increased from 20 W to max. 40 W if the mean speed is >
1000 rpm (mathemacal mean of the process speeds in
relaon to the motor speed, without standsll).
Rated power of brake resistor - W [10 ... 65535] W
Thermal capacity of brake
resistor
- kWs [0 ... 6553.5] kWs
Reducon of brake chopper
threshold
0 V [0 ... 150] V The threshold is reduced by the voltage value set here.
The switching threshold is adapted to the dierent mains
voltage ranges.
Reducon by 20 ... 30 V can prevent overvoltage for opera-
on in generator mode.
Impact of oscillaon damping 5.00 % [0.00 ... 250.00] % To suppress idle oscillaons. Typically, the impact has to be
increased for this purpose.
Oscillaon damping lter
me
50 ms [2 ... 250] ms
Before inial switch-on
•
That the drive does not show any visible signs of damage.
•
Is the mechanical xing o.k.?
•
Has the electrical connecon been implemented correctly?
•
Are all rotang parts and surfaces that may become hot protected against contact?
•
Is the featherkey radially secured during the test run without output elements?
•
Have all screwed connecons of the mechanical and electrical parts been ghtened?
•
Is it ensured that the cooling air can be freely supplied and discharged?
•
Has the PE conductor been connected correctly?
•
Has the "Seng of motor overload" been parameterised correctly?
•
Has the drive been parameterised correctly?
•
Are the electrical connecons ok?
•
Is a protecon against contact provided in front of rotang parts and in front of surfaces that can get hot?
•
Is the contact of good electrical conducvity if a PE connecon on the motor housing is used?
Commissioning
Before inial switch-on
61