EMC data
Actuaon on public supply systems
Implement measures to limit the radio
interference to be expected:
The machine or plant manufacturer is responsible for com-
pliance with the requirements for the machine/plant!
< 1 kW: with mains choke EN 61000-3-2
> 1 kW at mains current ≤ 16 A: without
addional measures
Mains current > 16 A: with mains choke or
mains lter, with dimensioning for rated
power. Rsce ≥ 120 is to be met.
EN 61000-3-12 RSCE: short-circuit power rao at the connecon point of
the machine/plant to the public network.
Noise emission
Category C2 EN 61800-3
Noise immunity
Meets requirement in compliance with EN 61800-3
Environmental condions
Climate
1K3 ( -30 °C ... +60 °C) EN 60721-3-1 Storage, < 3 months
1K3 ( -30 °C ... +40 °C) EN 60721-3-1 Storage, > 3 months
2K3 ( -30 °C ... +70 °C) EN 60721-3-2 Transport
3K3 ( -30 °C ... +40 °C)
In the case of very low-temperature appli-
caons without condensaon
EN 60721-3-3 operaon
Site altude
0 … 1000 m a.m.s.l. Without power reducon
1000 … 4000 m a.m.s.l. Reduce rated output current by 5 %/1000 m
Degree of polluon
Degree of polluon 2 EN 61800-5-1
Vibraon resistance
2M2 EN 60721-3-2 Transport
3M4 EN 60721-3-3 operaon
Vibraon severity
A EN 60034-14
Electrical supply condions
Possibility of connecon to dierent types of mains power supply enables worldwide use.
The following is supported:
3-phase mains connecon 400 V
3-phase mains connecon 480 V
Type of mains power supply
TT Mains power supplies with earthed start point
Voltage against earth: max. 300 V
TN
Technical data
Standards and operang condions
Electrical supply condions