Technical data
General data and operating conditions
2
EDK94AZHN26 DE/EN/FR/ES/IT 1.2
33
l
H1_Daten−Maße_mm
General data
Conformity and approval
Conformity
CE
73/23/EEC Low−Voltage Directive
Approval
UR UL 508C Industrial Control Equipment Recognised
(file no. E132659) for USA
Protection of persons and equipment
Enclosure EN 60529
IP00
Protective measures Against short circuit
Mounting conditions
Mounting place
In the control cabinet
Mounting position Vertically
Mounting clearances
Above/below
³ 25 mm
To the sides Side−by−side mounting without clearance
EMC
Noise emission EN 61800−3
Conducted, category C2.
Noise immunity EN 61800−3
Burst on mains cable: 2 kV/5 kHz
Burst on control cable: 2 kV/5 kHz
Surge on mains cable:
1 kV (1.2 ms/50 ms;
phase − phase)
2 kV (1.2 ms/50 ms;
phase − PE)