4 Electrical installation
Important notes
, During installation the notes given in the documentation for the standard
device must be observed!
( Stop!
Requirements on the brake cable (connection BD1/BD2):
ƒ If the brake cable is part of the motor cable, it must be shielded.
An operation with unshielded brake cables can destroy the motor brake
control module.
We recommend the use of Lenze system cables (motor cable with
separately shielded additional cores).
Connect the shield to PE on both sides.
ƒ When using a permanent magnet holding brake, ensure the correct
polarity of the brake cable.
If the terminals are reversed, the brake does not release. Since the motor
runs against the closed brake, the brake can be destroyed.
) Note!
The supply status can be reported to the standard device via the error channel.
For further information, please refer to the documentation of the standard
device.