RG-SDMOD 22
Drive Control & Communication
Parameter No.
1
smd
Register #
(hexadecimal
representation)
Parameter Name Range of Adjustment
2,
Modbus value (decimal value)
Factory
Default
PV400 PV507
C38 74 (4AH) 75 (4BH) Fixed Setpoint 2 (JOG2) 0 - 9990 (0.0 - 999) 30.0 Hz
C39 75 (4BH) 76 (4CH) Fixed Setpoint 3 (JOG3) 0 - 9990 (0.0 - 999) 40.0 Hz
C46 78 (4EH) 79 (4FH) Frequency Setpoint 0 - 2400 (0.0 - 240 Hz) Read Only
C50 79 (4FH) 80 (50H) Output Frequency 0 - 2400 (0.0 - 240 Hz) Read Only
C52 80 (50H) 82 (52H) Motor Voltage 0 - 255% Read Only
C53 81 (51H) 83 (53H) DC Bus Voltage 0 - 255% Read Only
C54 82 (52H) 84 (54H) Motor Current 0 - 255% Read Only
C56 83 (53H) 85 (55H) Drive Load 0 - 255% Read Only
C59 86 (56H) PI Actual Feedback c86 - c87 Read Only
C70 89 (59H) PI Proportional Gain 0 - 999 (0 - 99.9%) 5.0%
C71 90 (5AH) PI Integral Gain 0 - 999 (0 - 99.9 sec) 0.0 sec
C90 86 (56H) 92 (5CH) Input Voltage Selection 0 Auto
1 Low
2 High
0
C94 88 (58H) 94 (5EH) User Password 0 - 999 0
C99 89 (59H) 95 (5FH) Software Version Read 4 words (format 'SMD 1.51') Read Only
c01 96 (60H) Accel Rate 2 0 - 9990 (0.0 - 999 sec) 5.0 sec
c03 97 (61H) Decel Rate 2 0 - 9990 (0.0 - 999 sec) 5.0 sec
c06 90 (5AH) 98 (62H) Holding Time - Auto
DC Injection Brake
0 - 9990 (0.0 - 999 sec) 0.0 sec
c08 91 (5BH) 99 (63H) Analog Output Scaling 10 - 9990 (1.0 - 999) 100.0
c11 92 (5CH) 100 (64H) Configuration
Analog Output (62)
0 None
1 Output frequency 0 - 10V
2 Output frequency 2 - 10V
3 Load 0 - 10V
4 Load 2- 10V
5 Dynamic Braking
0
c17 93 (5DH) 101 (65H) Configuration
Digital Output (A1)
0 Ready
1 Fault
2 Motor is running
3 Motor is running - CW rotation
4 Motor is running - CCW rotation
5 Output frquency = 0Hz
6 Frequency setpoint reached
7 Threshold (C17) exceeded
8 Current limit reached
9 Feedback within min/max alarm range
10 Feedback outside min/max alarm range
0
c20 94 (5EH) 102 (66H) I
2
T Switch-Off 30 - 100% 100%
1 = The drive's programming code number; 2 = Selections in bold are for
smd
models with PV507 only.