5 RG-SDMOD
Introduction
D. The function codes supported by the
smd
drives are:
03 Read Holding Register (4X references). In general we can read only one register at a time. However,
there are a few limited exceptions.
Exception One:
Register #24 (Modbus Register #25) Drive Status, can also be read as a group of 6 words.
Exception Two:
Parameter C99 (Software Version) is a 4-word read.
04 Read Input Register (3X references). As with function 03, we read one register at a time except
where noted.
06 Preset Single Register (4X references). Write single register.
16 Preset Multiple Registers (4X references). Although the function is for multiple registers, we will
accept only a single register to be written.
Note: Since we do not differentiate between 4X and 3X references, function codes 03 and 04 are
treated identically.
E. Exception codes:
01 - Command rejected, Illegal function
02 - No such register
03 - Data out of range
04 - Wrong data format
06 - Slave device busy
F. The
smd
drive will most nearly conform to the Modicon
®
Micro 84 in capabilities. This may be of
importance when configuring networks for DDE Servers.
G.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com