WARNINGS AND CAUTIONS:
• Ifyouarenotsureaboutanypartoftheseinstructions,consultanelectrician.
• Cleanoutersurfacegentlywithdampclothonly.DO NOT usesoapsorcleaningliquids.
• Nouserserviceablecomponents.DO NOT attempttoserviceorrepair.
• UsethisdeviceWITH COPPER OR COPPER CLAD WIRE ONLY.
WARNINGS AND CAUTIONS:
• TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER AT CIRCUIT BREAKER OR FUSE AND TEST THAT THE
POWER IS OFF BEFORE WIRING!
• Tobeinstalledand/orusedinaccordancewithelectricalcodesandregulations.
• Toavoidoverheatingandpossibledamagetothisdeviceandotherequipment,DO NOTinstalltocontrolareceptacle.
• DO NOT controlaloadinexcessofspeciedratingsoryoumaydamageproperty,orcauseinjuryordeath.
RESET
RESET
TEST
TEST
1 2
0 3
Push down tabs per
diagram, one at a time and
rotate forward to release
1 2
0 3
1 2
0 3
Attach new face by inserting
bottom hinge tabs, then pivot
and snap the color kit to attach
Tools needed to install your Device
Changing the color of your device
Slotted/PhillipsScrewdriver ElectricalTape Pliers
Pencil Cutters Ruler
INSTALLING YOUR DEVICE
NOTE: UsecheckboxeswhenStepsarecompleted.
ONOFF
ONOFF
ONOFF
ONOFF
ONOFF
ONOFF
ONOFFONOFF
ONOFF
ONOFF
ONOFF
ONOFF
Step 1
WARNING:TO AVOID FIRE, SHOCK, OR DEATH;
TURN OFF POWERatcircuitbreakerorfuseandtest
thatpowerisoffbeforewiring!
2
4
3
1
Single-Pole
1. Line(Hot)
2. Neutral
3. Ground
4. Load
Step 2
Identifying your wiring application
(most common):
NOTE:Ifthewiringinthewallbox
doesnotresembleanyofthese
congurations,consultanelectrician.
WIRING SENSOR:
Connect wires per WIRING DIAGRAM as follows:
NOTE: Agroundconnectionisrequiredtooperate.Usethegroundwire
intheelectricalboxforgroundconnection.Ifthereisnogroundwire,
makesuretheelectricalboxisgroundedandattachthegroundwireto
theboxwithascrew.
• GreenorbarecopperwireinwallboxtoGreenterminalscrew.
• LineHotwallboxwiretoterminalscrewmarked"BK".
• Loadwallboxwiretoterminalscrewmarked"RD".
• ProceedtoStep5.
Hot (Black)
Neutral (White)
Red
Black
Black
White
LOAD
Line
120VAC, 60 Hz
Sensor
Green Ground
BK
RD
Terminal
Screw marked
Red (RD)
2
Terminal
Screw marked
Black (BK)
4
1
3
Single Pole Wiring Application:
Step 4
Single Pole Wide View Motion Activated Light Control
Cat.No.IPS05,IPV05-INDOORUSEONLY
Ratings:120VAC,60Hz600WIncandescent,5AResistive,150WLED&CFL,1/6HP
INSTALLATION INSTRUCTIONS
PK-93917-10-00-2A
FEATURES
• Cat.No.IPS05andIPV05haveasensingareaofcoverageof30ft.x
30ft.,andasensingangleof180
O
(seeSensingAreaCoveragegure
onpage2)
• Adjustablelightandtime-delaycontrolsarelocatedonthefrontofthe
device.Seeadjustmentsettingsectiononpage2fordetails.
• LEDindicatorisusedtoalerttheuserofthestatusofthedevice.
• AdjustableTimeDelaysettingfor30seconds,5minutes,
15minutesand30minutes.
LOCATION / MOUNTING
Thedevicerespondstotemperaturechangesandcareshouldbetaken
whenmountingthedevice.DO NOTmountdirectlyaboveaheatsource,
inalocationwherehotorcolddraftswillblowdirectlyonthesensor,or
whereunintendedmotion(e.g.,hallwaytrafc)willbewithinsensor’s
eld-of-view.
Preparing and connecting wires:
Thisdevicecanbewiredusingsidewireterminalscrews.
Chooseappropriatewirestrippingspecicationsaccordingly.
Strip Gage
(measure bare wire
here or use gage on
back of the sensor)
5/8”
(1.6 cm)
Cut
(if necessary)
Side Wire Connection
Sidewireterminalsaccept#14-12
AWGsolid copper wire only.
Step 3
Back Wire
Backwireopeningsuse#14-12
AWGsolid copper wire only.
BK
RD
YL 3-Way
Yourdevicemayincludecoloroptions.Tochangecoloroftheface
proceedasfollows:
• Makesurethattheendsofthewiresfromthewallboxarestraight
(cut if necessary).
• Removeinsulationfromeachwireinthewallboxasshown.
Question and Answer IconNeed help?

Do you have a question about the Leviton decora IPV05 and is the answer not in the manual?

Leviton decora IPV05 Specifications

General IconGeneral
StyleDecora
Voltage120 VAC
ColorWhite
Load TypeIncandescent, LED
Wattage500W Incandescent, 150W LED
WiringSingle Pole
Power SourceAC
Operating Temperature32°F to 104°F (0°C to 40°C)

Summary

General Information and Safety

Warnings and Cautions

Important safety notices regarding electrical shock, fire, and proper usage.

Product Features Overview

Key attributes of the motion-activated light control, including sensing capabilities.

Installation and Setup

Tools and Preparation

Lists required tools and initial steps like turning off power and preparing wires.

Wiring Applications and Connections

Details on identifying wiring configurations and connecting wires to the sensor terminals.

Installation Steps

Sequential guide for installing the device, from initial steps to final connections.

Device Mounting and Testing

Procedures for physically mounting the device, testing functionality, and securing the wallplate.

Adjustment Settings

How to configure light level sensitivity and time delay for optimal operation.

Operation Modes

Explanation of how the device operates in auto and manual modes for IPS05 and IPV05 models.

Troubleshooting and Support

Troubleshooting Guide

Solutions for common operational problems such as no light activation or lights staying on.

Technical Support and Warranty

Contact information for technical assistance and details of the limited 5-year warranty.