18 Floor Standing Type Air Conditioner
Operation Details
5-1. Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as
following.
• A point: The indoor pipe temperature to be less than B°C.
The indoor fan operates for minimum 10sec. even if the indoor pipe temperature falls lower than B°C.
During heating operation, the operating procedure of the indoor fan is as the following.
Step Indoor fan speed Pipe temp.
Off ≤22°C(Hot start operating)
Low ≥22°C
Selecting speed ≥C°C
Low ≤D°C
Off ≤20°C
Heat OFF Heat ON
Indoor Temp. Indoor Temp.
15°C 20°C 20°C 15°C 20°C 20°C
C°C32°C34°C36°C30°C31°C33°C
D°C28°C30°C32°C26°C28°C30°C
B°C27°C29°C31°C- - -