Service Manual 19
Operation Details
6. Hot-Start Control
The indoor fan stops until the evaporator piping temperature will be reached to 28°C.
During heating operation, if piping temperatures fall below 26°C fan stops.
The operation diagram is as following.
7. Defrost Control
Defrost operation is controlled by timer and sensing temperature of outdoor pipe.
The first defrost starts only when the outdoor pipe temperature falls below -6°C after 45 minutes passed from
starting of heating operation and more than.
Defrost ends after 10 minutes pass from starting of defrost operation or when the outdoor pipe temperature rises
over 12°C even if before 10 minutes.
The second defrost starts only when the outdoor pipe temperature falls below -6°C after 45 minutes pass from
ending of the first defrost and more than.