ELECTRICAL WIRING
71
ENGLISH
Display Title Cause of Error
Outdoor unit related error
2 6
Outdoor Unit Inverter Compressor
Start Failure
The First Start Failure by Outdoor Unit Inverter
Compressor Abnormality
2 9
Outdoor Unit Inverter Compressor
Over Current
Outdoor Unit Inverter Compressor Fault OR Drive Fault
3 2
Outdoor Unit Inverter Compressor1
High Discharge Temperature
Outdoor Unit Inverter Compressor1 High Discharge
Temperature
3 4 High Pressure of Outdoor Unit High Pressure of Outdoor Unit
3 5 Low Pressure of Outdoor Unit Low Pressure of Outdoor Unit
3 6
Outdoor Unit Low Compression Ratio
Limited
Outdoor Unit Low Compression Ratio Limited
4 0
Outdoor Unit Inverter Compressor CT
Sensor Fault
Outdoor Unit Inverter Compressor CT Sensor open
or short
4 1
Outdoor Unit Inverter Compressor1
Discharge Temperature Sensor Fault
Outdoor Unit Inverter Compressor Discharge
Temperature Sensor open or short
4 2
Outdoor Unit Low Pressure Sensor
Fault
Outdoor Unit Low Pressure Sensor open or short
4 3
Outdoor Unit High Pressure Sensor
Fault
Outdoor Unit High Pressure Sensor open or short
4 4
Outdoor Unit Air Temperature Sensor
Fault
Outdoor Unit Air Temperature Sensor open or short
4 5
Outdoor Unit Heat Exchanger
Temperature Sensor (Front side) Fault
Outdoor Unit Heat Exchanger Temperature
Sensor(Front side) open or short
4 6
Outdoor Unit Suction Temperature
Sensor Fault
Outdoor Unit Suction Temperature Sensor open or
short
5 0
Omitting connection of R, S, T power
of Outdoor Unit
Omitting connection of outdoor unit
5 1 Excessive capacity of indoor units
Excessive connection of indoor units compared to
capacity of Outdoor Unit
5 2
Communication error : inverter PCB →
Main PCB
Failing to receive inverter signal at main PCB of
Outdoor Unit
5 3
Communication error : indoor unit →
Main PCB of Outdoor Unit
Failing to receive indoor unit signal at main PCB of
Outdoor Unit.
5 7
Communication error : Main PCB →
inverter PCB
Failing to receive signal main PCB at inverter PCB of
Outdoor Unit
6 0
Inverter PCB EEPROM Error of Master
Outdoor Unit
Access Error of Inverter PCB of Outdoor Unit
6 2
Outdoor Unit Inverter Heatsink High
Temperature
System is turned off by Outdoor Unit Inverter Heatsink
High Temperature
6 5
Outdoor Unit Inverter Heatsink
Temperature Sensor Fault
Outdoor Unit Inverter Heatsink Temperature Sensor
open or short