EasyManuals Logo

LG ARUN040GSS5 User Manual

LG ARUN040GSS5
77 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #71 background imageLoading...
Page #71 background image
ELECTRICAL WIRING
71
ENGLISH
Display Title Cause of Error
Outdoor unit related error
2 6
Outdoor Unit Inverter Compressor
Start Failure
The First Start Failure by Outdoor Unit Inverter
Compressor Abnormality
2 9
Outdoor Unit Inverter Compressor
Over Current
Outdoor Unit Inverter Compressor Fault OR Drive Fault
3 2
Outdoor Unit Inverter Compressor1
High Discharge Temperature
Outdoor Unit Inverter Compressor1 High Discharge
Temperature
3 4 High Pressure of Outdoor Unit High Pressure of Outdoor Unit
3 5 Low Pressure of Outdoor Unit Low Pressure of Outdoor Unit
3 6
Outdoor Unit Low Compression Ratio
Limited
Outdoor Unit Low Compression Ratio Limited
4 0
Outdoor Unit Inverter Compressor CT
Sensor Fault
Outdoor Unit Inverter Compressor CT Sensor open
or short
4 1
Outdoor Unit Inverter Compressor1
Discharge Temperature Sensor Fault
Outdoor Unit Inverter Compressor Discharge
Temperature Sensor open or short
4 2
Outdoor Unit Low Pressure Sensor
Fault
Outdoor Unit Low Pressure Sensor open or short
4 3
Outdoor Unit High Pressure Sensor
Fault
Outdoor Unit High Pressure Sensor open or short
4 4
Outdoor Unit Air Temperature Sensor
Fault
Outdoor Unit Air Temperature Sensor open or short
4 5
Outdoor Unit Heat Exchanger
Temperature Sensor (Front side) Fault
Outdoor Unit Heat Exchanger Temperature
Sensor(Front side) open or short
4 6
Outdoor Unit Suction Temperature
Sensor Fault
Outdoor Unit Suction Temperature Sensor open or
short
5 0
Omitting connection of R, S, T power
of Outdoor Unit
Omitting connection of outdoor unit
5 1 Excessive capacity of indoor units
Excessive connection of indoor units compared to
capacity of Outdoor Unit
5 2
Communication error : inverter PCB
Main PCB
Failing to receive inverter signal at main PCB of
Outdoor Unit
5 3
Communication error : indoor unit
Main PCB of Outdoor Unit
Failing to receive indoor unit signal at main PCB of
Outdoor Unit.
5 7
Communication error : Main PCB
inverter PCB
Failing to receive signal main PCB at inverter PCB of
Outdoor Unit
6 0
Inverter PCB EEPROM Error of Master
Outdoor Unit
Access Error of Inverter PCB of Outdoor Unit
6 2
Outdoor Unit Inverter Heatsink High
Temperature
System is turned off by Outdoor Unit Inverter Heatsink
High Temperature
6 5
Outdoor Unit Inverter Heatsink
Temperature Sensor Fault
Outdoor Unit Inverter Heatsink Temperature Sensor
open or short

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LG ARUN040GSS5 and is the answer not in the manual?

LG ARUN040GSS5 Specifications

General IconGeneral
BrandLG
ModelARUN040GSS5
CategoryAir Conditioner
LanguageEnglish

Related product manuals