EasyManua.ls Logo

LG ARUN40LS2A - Page 12

LG ARUN40LS2A
35 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12
ENGLISH
Cautions for Handling Service Valve
- The service valves are closed at shipment from the factory
How to Use the Shut-Off Valve
Use hexagonal wrenches 4mm or 6mm
Opening the valve
- Place the hexagon wrench on the valve bar and turn counter-clock-
wise.
- Stop when the valve bar no longer turns. It is now open.
Closing the valve
- Place the hexagon wrench on the valve bar and turn clockwise.
- Stop when the valve bar no longer turns. It is now closed.
CAUTION
Make sure to keep the valve open during operation.
!
Refrigerant pipe connection torque
Pipe external
diameter
6.35mm
(1/4")
9.52mm
(3/8")
12.7mm
(1/2")
15.88mm
(5/8")
Torque
180~250
kgf.cm
340~420
kgf.cm
550~660
kgf.cm
630~820
kgf.cm
The names of parts of the service valve are shown in the figure.
Since the side boards may be deformed if only a torque wrench is
used when loosening or tightening flare nuts, always lock the shut-off
valve with a wrench and then use a torque wrench.
Do not place wrenches on the valve cover.
Do not apply force on the valve cover, this may result in a refrigerant
leak.
1
2
3
4
1
2
1. Service point
2. Shut-off Valve
3. Filed piping connection
4. Valve cover
1. Spanner
2. Torque wrench
Direction to open Direction to open
<Liquid pipe> <Gas pipe>
CAUTION
1 Use the following materials for refrigerant piping.
• Material: Seamless phosphorous deoxidized copper pipe
• Wall thickness : Comply with the relevant local and national regu-
lations for the designed pressure 3.8MPa. We
recommend the following table as the minimum
wall thickness.
2 Commercially available piping often contains dust and other materi-
als. Always blow it clean with a dry inert gas.
3 Use care to prevent dust, water or other contaminants from enter-
ing the piping during installation.
4 Reduce the number of bending portions as much as possible, and
make bending radius as big as possible.
5 Always use the branch piping set shown below, which are sold sep-
arately.
6 If the diameters of the branch piping of the designated refrigerant
piping differs, use a pipe cutter to cut the connecting section and
then use an adapter for connecting different diameters to connect
the piping.
7 Always observe the restrictions on the refrigerant piping (such as
rated length, difference in height, and piping diameter).
Failure to do so can result in equipment failure or a decline in heat-
ing/cooling performance.
8 A second branch cannot be made after a header. (These are shown
by .)
Outer diameter
[mm]
6.35 9.52 12.7 15.88 19.05 22.2 25.4 28.58 31.8 34.9 38.1 41.3
Minimum
thickness [mm]
0.8 0.8 0.8 0.99 0.99 0.99 0.99 0.99 1.1 1.21 1.35 1.43
Y branch
Header
4 branch 7 branch 10 branch
ARBLB01621, ARBLB03321,
ARBLB07121, ARBLB14521,
ARBLB23220
ARBL054 ARBL057 ARBL1010
ARBL104 ARBL107 ARBL2010
A
A
B
To Outdoor Unit
Sealed Piping

Related product manuals