78 Outside Unit
Test Run
Display
Error item Root cause of error
number
Initial operation failure due to slave2 outside unit inverter compressor
error
Compressor turned Off due to master outside unit inverter DC voltage
over-charge
Compressor turned Off due to slave1 outside unit inverter DC voltage
over-charge
Compressor turned Off due to slave2 outside unit inverter DC voltage
over-charge
Master outside unit inverter compressor error or operating component
(IPM) error operation
Slave1 outside unit inverter compressor error or operating component
(IPM) error operation
Slave2 outside unit inverter compressor error or operating component
(IPM) error operation
Compressor turned off due to master outside unit inverter CT under-
current
Compressor turned off due to slave1 outside unit inverter CT under-
current
Compressor turned off due to slave1 outside unit inverter CT under-
current
Compressor turned off due to master outside unit inverter compressor
discharge temperature over-rise
Flow rate insufficiency or flow switch trouble of master outside unit
Compressor turned off due to slave1 outside unit inverter compressor
discharge temperature over-rise
Flow rate insufficiency or flow switch trouble of slave1 outside unit
Compressor turned off due to slave2 outside unit inverter compressor
discharge temperature over-rise
Flow rate insufficiency or flow switch trouble of slave2 outside unit
Compressor turned off due to master outside unit static speed com-
pressor discharge temperature over-rise
Compressor turned off due to slave1 outside unit static speed com-
pressor discharge temperature over-rise
Compressor turned off due to slave2 outside unit static speed com-
pressor discharge temperature over-rise
Compressor turned off due to master outside unit high pressure over-rise
Flow rate insufficiency or flow switch trouble of master outside unit
Compressor turned off due to slave1 outside unit high pressure over-rise
Flow rate insufficiency or flow switch trouble of slave1 outside unit
Compressor turned off due to slave2 outside unit high pressure over-rise
Flow rate insufficiency or flow switch trouble of slave2 outside unit
Compressor turned off due to master outside unit low pressure over-
drop.
Compressor turned off due to slave1 outside unit low pressure over-drop.
Compressor turned off due to slave2 outside unit low pressure over-drop.
Master outside unit inverter compressor current detection (CT) sensor
disconnection or short circuit
Slave1 outside unit inverter compressor current detection (CT) sensor
disconnection or short circuit
Slave2 outside unit inverter compressor current detection (CT) sensor
disconnection or short circuit
Master outside unit inverter compressor discharge temperature sensor
disconnection or short circuit
263
Slave2 outside unit inverter compressor opera-
tion failure error
281
Master outside unit inverter DC link over-volt-
age error
282
Slave1 outside unit inverter DC link over-volt-
age error
283
Slave2 outside unit inverter DC link over-volt-
age error
291
Master outside unit inverter compressor over-
current
292
Slave1 outside unit inverter compressor over-
current
293
Slave2 outside unit inverter compressor over-
current
311
Master outside unit inverter CT under-current
error
312
Slave1 outside unit inverter CT under-current
error
313
Slave1 outside unit inverter CT under-current
error
321
Master outside unit inverter compressor dis-
charge temperature over-rise
322
Slave1 outside unit inverter compressor dis-
charge temperature over-rise
323
Slave2 outside unit inverter compressor dis-
charge temperature over-rise
331
Master outside unit static speed compressor
discharge temperature over-rise
332
Slave1 outside unit static speed compressor
discharge temperature over-rise
333
Slave2 outside unit static speed compressor
discharge temperature over-rise
3 4 1 Master outside unit high pressure over-rise
3 4 2 Slave1 outside unit high pressure over-rise
3 4 3 Slave2 outside unit high pressure over-rise
3 5 1 Master outside unit low pressure over-drop.
3 5 2 Slave1 outside unit low pressure over-drop.
3 5 3 Slave2 outside unit low pressure over-drop.
401
Master outside unit inverter compressor CT
sensor error
402
Slave1 outside unit inverter compressor CT
sensor error
403
Slave2 outside unit inverter compressor CT
sensor error
411
Master outside unit inverter compressor dis-
charge temperature sensor error