Operation
• Operating frequency of compressor depend on the difference of the temperature
(= compressor off temp. - intake air temp.)
• Compressor off temp. = setting temp. +4°C
on temp. = setting temp. +2°C
• If compressor operates at some operation frequency, the operating frequency of compressor cannot be
changed within 30 seconds.
• Condition of compressor turned off
- When intake air temperature reaches +4°C above the setting temperature.
• Condition of indoor fan turned off
- While in compressor on:indoor pipe temp. < 20°C
• While in defrost control, between the indoor and outdoor fans are turned off.
• Compressor 2minutes delay
- After compressor off, the compressor can restart minimum 2 minutes later.
Temp. differences
2.5~3.0°C
2.0~2.49°C
1.5~1.99°C
1.0~1.49°C
0.5~0.99°C
0.0~0.49°C
-0.5~0°C
Comp. Operating frequency
Step 1
Step 2
Step 3
Step 4
Step 5
Step 6
Step 7
[ The operating freq. step of comp]
[The targeting operating freq. of comp. each model]
Heating mode operation
Model
AS-W0964DH0/DH1/GH0 35 44 53 62 69 74 80
AS-W1264DH0/GH0 20 38 53 63 72 79 86
AS-W1865DH0 16 38 47 65 79 87 96
AS-W1224DH0 20 35 53 63 70 79 86
AS-W1424DH0 20 35 53 63 77 79 86
AS-W1825DH0 16 38 47 62 79 87 90
AS-W096E1G0 35 40 48 56 65 90 94
AS-W126E1G0 35 40 48 56 80 90 94
Comp. Operating frequency
Step 1 Step 2 Step 3 Step 4 Step 5 Step 6 Step 7
• While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the
other mode operation(cooling, dehumidification, ventilation), the Jet Cool mode is operated.
• In the Jet Cool mode, the indoor fan is operated super-high speed for 30 min. at cooling mode operation.
• In the Jet Cool mode, the room temperature is controlled to the setting temperature, 18°C.
• When the sleep timer mode input while the Jet Cool mode operation, the Jet Cool mode has the priority.
• When the Jet Cool key is input, the upper/lower vane is reset to those of the initial cooling mode and then
operated in order that the air outflow could reach further.
Jet cool mode operation