4.1 E.S.P. (External Static Pressure) Setting
4. Installation Functions
Function Code Pressure
Press button for 4 seconds to enter the installer
setting mode until timer segment displays “01:01”.
1
Select static pressure by pressing button.
(01:V-H, 02:F-H, 03:V-L, 04:F-L)
3
Press button to save.
4
5
Pressing button will exit settings mode.
After setup, it automatically gets out of setup mode if there is no button
input for 25 seconds.
When exiting without pressing set button, the manipulated value is not
reflected.
If pressing button repeatedly, it moves to static pressure
selection menu as picture below.
2
This function is applied to only duct type. Setting this in other cases will cause malfunction.
<Static Pressure Setting Table>
Part 2 Functions & Controls
Pressure selection
Function
Zone state ESP standard value
01 V-H Variable High
02 F-H Fixed High
03 V-L Variable Low
04 F-L Fixed Low

Table of Contents

Other manuals for LG CM24 N14

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LG CM24 N14 and is the answer not in the manual?

LG CM24 N14 Specifications

General IconGeneral
BrandLG
ModelCM24 N14
CategoryAir Conditioner
LanguageEnglish

Related product manuals