INSTALLATION COMPOSITION
ENGLISH
INSTALLATION COMPOSITION
Liquid pipe
Gas pipe
Refrigerant pipe
Pipe sensor
Communication cable
Refrigerant flow (air conditioning)
Refrigerant flow (heating)
This EEV KIT is a product that connects an AHU with an outdoor unit with the following
composition.
installation components
No. Name Notes
1 AIR HANDLING UNIT -
2 AHU EEV KIT
Connectible outdoor unit capacity
PRLK396A0 22 ~ 40 HP
PRLK594A0 42 ~ 60 HP
3 AHU Comm. KIT -
4 Outdoor unit MULTI V
5 Pipe sensor_IN Sensor: Ø 5, length: 5m, cable color: Black
6 Pipe sensor_OUT Sensor: Ø 7, length: 5m, cable color: Red
7 90˚ elbow
PRLK396A0 Ø19.05 (5/8")
PRLK594A0 Ø19.05 (5/8")