LG GR-151SPF - NO COOLING DIAGNOSIS; Troubleshooting Flowchart for Cooling Issues

LG GR-151SPF
13 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NO COOLING
The Compressor ]__
doesn't run.
Check if the current I_
flows at the contacting Poor contacting point
point of the Thermostat.
tcheckthecurrentI___,tShorted
-_ flowing of starting Broken
system.
Check if the current
"_) flows at the main coil of Coil shorted
the Compressor.
H
H
H
Replace the
Thermostat.
Replace the device.
Replace the
Compressor.
.___. Check the components
on the main circuit.
_ Replace the
components.
J
Poor running of the
Compressor.
Measure the starting I_ H
voltage. Low voltage
Check if the current _4_ H
flows at the contacting Poor contacting point
point of the starting and broken
system.
tChoc if' eco rent H oo'aoe' e
"--) flowing of the sub coil of Shorted
Compressor.
the Compressor.
Increase the voltage.
Replace the device.
t ls the current amount of I .I The coil of the I .I Repair the
the electric components i_ Compressor Motor is _1 Compressor.
normal? worn out.
Compressor runs.
I i
Frost doesn't form at the I ,J
Evaporator when
operating set for more
than 30 min.
Refrigerant leaks. H
Poor compressing.
Repair the
Compressor.