COMPRESSOR AND ANOTHER ELECTRIC COMPONENTS
[_ Power Source I
Separate the PTC-STARTER from
the Compressor and measure the
voltage between M and C of the
Compressor.
The applied voltage is not in the
range of Rating Voltage _+10%.
_[ qual to the applied
voltage. (Rating
voltage _+10%)
H dvice the customer
to use in the fixed
range.
Check the
resistance of the
Compressor Motor.
Test the resistance among
M-C, S-C, and M-S.
Replace the Compressor.
YES
11
[_ Check the I I Test the resistance of the both
resistance of the J_l terminals in the PTC-STARTER.
PTC.
YES ,[_
Check OLR
NO
Check if applying a 1._
regular OLR
NO
Replace the
PTC-STARTER.
OLP works within 30 sec.
in forcible OLP operation
by turning instant power on
and off.
I
YES ,_.
NO ,_ Replace OLP.
f
Check the
starting state.
Measure minimum starting voltage
after checking steps 1-3 above.
And measure the pressure balance
of the PTC with the interval of
more than 5 min.
._ Starts at the voltage
of 85% below.
Normal.
Starts at the voltage of
more than 90%.
____ Check the starting
state at the regular
voltage above.
,_NO
Replace the PTC.
Normal.
J