60 Room Air Conditioner
The phenomena in case of connecting error
INDOOR UNIT
Connector Type
Condition
Open and connecting error
Open
Open
Open
Open
Short between terminals
(③ and ④) of ROOM-TH.
Short between terminals
(① and ②) of PIPE-TH.
Open
Short between terminals
Short between terminals
• The same as the phenomenon of Outdoor Unit.
• The up/down vane does not operate.
• The up/down vane does not smoothly operate.
• It does not operate with a remote controller.
• The operation indicator blinks once
(on for 0.5 second, off for 3 seconds).
• The compressor operates continuously regardless
of the setting temperature and the variation of room
temperature.
• The operation indicator blinks once
(on for 0.5 second, off for 3 seconds)
• Continuous operation
• The Left/Right vane does not operate.
• The Left/Right vane does not smoothly operate.
• The operation indicator blinks once.
• The compressor and the outdoor fan stop.
• The indoor fan speed is low.
• The indoor fan does not operate.
• The operation indicator of Indoor unit blinks 8 times.
CN-DC/DC
CN-MOTOR
CN-U/D
CN-DISP1
CN-TH
CN-L/R
① Blue
② Black
③ Brown
④ Red
Phenomena
①②③④
On for 0.5 second
Off for 3 seconds
Troubleshooting Guide