PERFORMANCE DATA
Cooling Capacity Tables
Table 18: LC098HV4 System Cooling Capacity Table.
Model No. /
Nominal Capacity
(Btu/h)
Outdoor
Air Temp.
(°F DB)
Indoor Air Temp. °F DB / °F WB
68 / 57 73 / 61 77 / 64 80 / 67 86 / 72 90 / 75
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
LC098HV4 /
9,000
-4 8.85 6.84 0.39 9.40 7.23 0.40 9.95 7.00 0.42 10.34 7.15 0.42 11.05 7.21 0.43 11.60 7.34 0.44
0 8.84 6.88 0.39 9.39 7.27 0.41 9.94 7.04 0.42 10.34 7.19 0.43 11.04 7.25 0.44 11.59 7.39 0.45
5 8.84 6.94 0.40 9.38 7.33 0.42 9.93 7.10 0.43 10.33 7.25 0.44 11.03 7.31 0.44 11.58 7.45 0.45
10 8.83 7.00 0.41 9.38 7.39 0.42 9.93 7.16 0.44 10.32 7.31 0.44 11.02 7.37 0.45 11.57 7.51 0.46
15 8.82 7.05 0.41 9.37 7.45 0.43 9.92 7.21 0.44 10.31 7.37 0.45 11.01 7.43 0.46 11.56 7.57 0.47
20 8.82 7.11 0.42 9.36 7.51 0.43 9.91 7.27 0.45 10.31 7.42 0.46 11.01 7.49 0.46 11.55 7.63 0.47
25 8.81 7.16 0.42 9.36 7.57 0.44 9.90 7.33 0.46 10.30 7.48 0.46 11.00 7.54 0.47 11.54 7.69 0.48
30 8.80 7.22 0.43 9.35 7.63 0.45 9.90 7.38 0.46 10.29 7.54 0.47 10.99 7.60 0.48 11.54 7.75 0.49
35 8.80 7.27 0.44 9.34 7.68 0.45 9.89 7.44 0.47 10.28 7.60 0.47 10.98 7.66 0.48 11.53 7.81 0.49
40 8.79 7.33 0.44 9.33 7.74 0.46 9.88 7.50 0.48 10.27 7.65 0.48 10.97 7.72 0.49 11.52 7.86 0.50
45 8.78 7.38 0.45 9.33 7.80 0.47 9.87 7.55 0.48 10.27 7.71 0.49 10.96 7.78 0.50 11.51 7.92 0.51
50 8.78 7.44 0.45 9.32 7.86 0.47 9.87 7.61 0.49 10.26 7.77 0.49 10.96 7.83 0.50 11.50 7.98 0.51
55 8.77 7.49 0.46 9.31 7.91 0.48 9.86 7.66 0.49 10.25 7.82 0.50 10.95 7.89 0.51 11.49 8.04 0.52
60 8.76 7.55 0.47 9.31 7.97 0.48 9.85 7.72 0.50 10.24 7.88 0.51 10.94 7.95 0.52 11.48 8.10 0.53
65 8.76 7.60 0.47 9.30 8.03 0.49 9.84 7.77 0.51 10.24 7.94 0.51 10.93 8.00 0.52 11.47 8.16 0.53
70 8.75 7.65 0.48 9.29 8.09 0.50 9.84 7.83 0.51 10.23 7.99 0.52 10.92 8.06 0.53 11.47 8.21 0.54
75 8.54 7.53 0.50 9.08 7.96 0.52 9.62 7.72 0.54 10.01 7.89 0.55 10.71 7.96 0.56 11.25 8.12 0.57
80 8.33 7.40 0.53 8.87 7.84 0.55 9.41 7.61 0.57 9.80 7.78 0.58 10.49 7.86 0.59 11.03 8.03 0.60
85 8.12 7.27 0.56 8.66 7.71 0.58 9.20 7.49 0.60 9.59 7.66 0.60 10.28 7.76 0.62 10.82 7.92 0.63
90 7.91 7.13 0.58 8.45 7.57 0.60 8.99 7.37 0.62 9.37 7.55 0.63 10.06 7.65 0.64 10.60 7.82 0.66
95 7.68 7.05 0.61 8.22 7.50 0.63 8.75 7.31 0.65 9.00 7.38 0.66 9.83 7.61 0.67 10.36 7.79 0.69
100 7.50 6.86 0.63 8.03 7.31 0.66 8.57 7.14 0.68 8.88 7.27 0.69 9.64 7.44 0.70 10.17 7.63 0.72
105 7.31 6.68 0.66 7.84 7.13 0.68 8.38 6.96 0.71 8.77 7.15 0.72 9.45 7.28 0.73 9.99 7.47 0.74
110 7.12 6.45 0.68 7.66 6.89 0.71 8.19 6.75 0.74 8.58 6.94 0.74 9.26 7.07 0.76 9.80 7.26 0.77
115 6.94 6.25 0.71 7.47 6.70 0.74 8.01 6.57 0.76 8.39 6.76 0.77 9.08 6.90 0.79 9.61 7.10 0.80
118 6.82 6.21 0.73 7.36 6.66 0.75 7.89 6.54 0.78 8.28 6.73 0.79 8.96 6.88 0.80 9.50 7.08 0.82
122 6.79 6.19 0.75 7.32 6.65 0.77 7.86 6.52 0.80 8.24 6.72 0.81 8.93 6.87 0.83 9.46 7.07 0.84
TC = Total Capacity (kBtu/h).
SHC: Sensible Heat Capacity (kBtu/h).
PI = Power input (KW). Power input (KW) includes compressor and fan(s).
Nominal capacity as rated 0 ft. above sea level and a 0 ft. level difference between outdoor and indoor
unit. Corresponding refrigerant piping length is accordance with standard length of each outdoor unit.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF
wet bulb (WB), and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
Cooling range can be extended from 0°F down to -4°F using the Low Ambient Wind Baffle Kit (sold
separately).
The shaded table rows indicate reference data. When operating at this temperature, these values can
be different if the system is not running consistently.