(1) The function of main control
1. Time delay Safety Control
• 3min.; The compressor operation is delayed for 3 minutes to balance the pressure of cycle.
(Protection of compressor)
• 5sec.;
The indoor fan is delayed for 5 seconds, when operating initially, to prevent noises occurred by the vertical
louver and wind.
• 2min.; The reversing valve is delayed for 2 minutes to prevent the refrigerant-gas for abnormal noise when the
heating operation is OFF or switched to the other operation mode while compressor is off.
While compressor is running, it takes 3~5 seconds to switch.
2. Chaos Swing Mode
• By the Chaos Swing key input, the upper/lower vane automatically operates with the Chaos Swing or they are
fixed to the desired direction.
• While in Chaos Swing mode, the angles of cooling and heating cycle operations are different.
- 15 -
Operation Details
INTAKE AIR TEMP.
SETTING TEMP. +1
°
F
(Compressor ON)
SETTING TEMP. -1
°
F
(Compressor OFF)
Setting
fan speed
Setting
fan speed
More than
3 minutes
More than
3 minutes
Setting
fan speed
COMPRESSOR ON OFF ON OFF ON
INDOOR FAN SPEED Low Low
■ Protection of the indoor heat exchanger from frosting
• Compressor and outdoor fan stop when indoor pipe temperature is below 0°C(32°F) and restart at the pipe
temperature is above 7°C(45°F).
3. Cooling Operation Mode
• When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the
remote control and the operation diagram is shown below.