Does the LED01M of outdoor PCB Ass'y
blink 6 times?
Check the state of connecting cable (3 line)
between indoor and outdoor uint.
When compressor does not operate normally.
DC Peak Error(Error Code )
Trouble 7-1
NO
YES
Is the connecting state of connectors in
outdoor Sub. PCB Ass'y right?
(CN-UVW, CN-IPM)
Electrical wiring diagram (Colors)
Check the connecting state of connectors
in PCB Ass'y(Main/Sub)
If CN-UWV is connected, the comprressor
can be operated a opposite direction.
NO
YES
Is the power module in Sub PCB Ass'y
right?
Check the short P-N P-U, V, W, and N-U,
V, W of IPM and then collector, emiter of
IGBT
Replace the Sub PCB Ass'y.
NO
YES
Is the voltage of CN-AC over than
AC170V?
Check the supplied voltage.
NO
YES
Is the voltage of CN-DC over than about
DC380V?
Check CN-IPM connector(Pin No. 12)
Replace the Sub PCB Ass'y.
NO
YES
Is the refrigerant pressure right?
Replace the PCB Ass'y.
Main PCB Ass'y
Sub PCB Ass'y
Control Box Ass'y
Supply the refrigerant.
NO
NO