-63-
When compressor does not oprate normally.
■ Communication error between Indoor and Outdoor (Error Code ➄)
Trouble 7-2
Does the operating LED in display PCB
Ass'y blink 5 times?
• Check the state of connecting cable
(3 line) bewteen indoor and outdoor unit .
• Check Fuse, Noise Filter, PTC, etc.
NO
YES
Is the voltage of CN-POWER Pin No. 1,2
AC220/240V in Main PCB Ass'y.
• Electrical wiring diagram(Colors)
• Check the connecting state
of connectors in outdoor PCB Ass'y
(Main/Sub)
• Check the Fuse of outdoor Control Box.
NO
YES
Is the voltage of CN-AC AC220/240V in
SUB PCB Ass'y?
• Check the connecting state of connectors
in PCB Ass'y(Main/Sub).
NO
YES
Is the voltage of CN-DC over than
DC350V?
Replace the Sub PCB Ass'y.
NO
YES
Is the connection of CN-DATA between
indoor and outdoor unit right?
Replace the PCB Ass'y.
• Main PCB Ass'y (Indoor/Outdoor)
• Control Box Ass'y.
• Reconnect the cable to terminal block.
• Check the PCB pattern(Resoldering).
NO
YES