Refrigeration Cycle Diagram
• HEAT PUMP
Rated performance for refrigerant line length of: 7.5m
If 18K Capacity is installed at a distance of 15m, 187.5g of refrigerant
should be added ....................................................(15-7.5)x25g
- 12 -
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
INDOOR UNIT
H/EX
Liquid SideGas Side
COMPRESSOR
VALVE REVERSING
ACCUM.
H/EX
Gas SideLiquid Side
CAPI C1
CAPI A
CAPI B
Heating Cooring
CAPI C2
(
OUTDOOR UNIT
GAS LIQUID
Elevation (m)
Length (m)
* Additional
refrigerant
(g/m)
Pipe Size
Rated Rated
Max. Max.
Capacity
18K 5/8" 1/4"
7.
5 50 5 30 25
24K 5/8" 1/4"
7.5 50 5 30 30