24 Ventilator
Wiring Connection
Motor
Driver
PCB
Terminal Block 2
Sub PCB
Main PCB
Terminal Block 1
Power
Supply
Wiring
Remote
Controller
Wiring
Additional
Parts
Wiring
screw
Clamp
Clamp
screw
Clamp
screw
• See “Label Circuit” on the backside of the cover of control box for electric wiring work.
• Be sure to attach the sealing material or putty (locally procured) to hole of wiring to prevent the
infiltration of water as well as any insects and other small creatures from outside. Otherwise a
short-circuit may occur inside the control box.
• When clamping the wires, be sure no pressure is applied to the wire connections by using the
included clamping material to make appropriate clamps. Also, when wiring, make sure the lid on
the control box fits snugly by arranging the wires neatly and attaching the control box cover firm-
ly. When attaching the cover of control box, make sure no wires get caught in the edges. Pass
wiring through the wiring through holes to prevent damage to them.
• Make sure the remote controller wiring, the wiring between the units, and other electrical wiring
do not pass through the same locations outside of the unit, separating them by at least 50mm,
otherwise electrical noise (external static) could cause mistaken operation or breakage.
CAUTION
Clamping of cables
1) Arrange 2 power cables on the control panel.
2) First, fasten the Plastic clamp with screw to the inner boss of control panel.