28 Ventilator
Installer Setting Code and Value Table
■ Test Run
1. Function explanation: when installing the product, test operation for checking the installation sta-
tus
2. When setting test operation, LCD Display
2.1) cooling, normal, super-high mode, temperature setting 88Seg 'LO', extra operation
2.2) when setting test operation, after test operating for 18 minutes, auto cancellation
2.3) during test operation, extra operation control available (including ventilation KIT)
■ Setting Address of Central Control
1. Function explanation: when connecting central control, it sets the address of central control
address of indoor unit.
2. Function control and setting
2.1) Select the address code with inputting the up-down button. (0~F)
2.2) Change the items with inputting the right-left button.
(Group address ↔ indoor unit address)
2.3) Set the address with inputting Setting/Cancel button.(Indoor data send)
※ DX : Direct expansion ventilation
General : General ventilation
No. Function Code Available Product Value
1 Test run 01 DX 01: Test run setting
2
Setting Address of
02 General/DX 00~FF : Address of central control
Central Control
3 Supply ESP 03
General/DX
Value1 – Step(01:low, 02:high, 03:super high)
4 Exhaust ESP 04 Value2 – ESP value(0~255)
5 Product direction 05 General 01:Normal, 02:Reverse
6 Quick Refresh Priority 06 General/DX 01:Supply air first, 02:Exhaust air first
7 Master setting 07 General/DX 00:Slave, 01:Master
8 Override setting 08 DX 00:Slave, 01:Master
9 Dry Contact Auto 09 General/DX 00:OFF, 01:ON
10 Release of 3Min. Delay 10 General/DX 01:Set
11 Zone State 11 DX 01:Variable, 02:Fixed
12 Selecting °C or F 12 DX 00:Celsius , 01:Fahrenheit
13
Humidification for
13 DX
00 : Not in use
Singlar Ventilation 01 : Use
14
Humidification for
14 DX 01:Automatic, 02:Manual
Heat Mode Ventilation
Field Setting and Test Run