Field Setting and Test Run
Installation Manual 27
ENGLISH
1. Function Explanation
- After installation by the installer, it performs the function for product setting.
2. Setting
1) function entry
1.1) Input the Function setting button for 3 seconds to enter the installer setting mode.
1.2) When entering, LCD other than relevant LCD is not appeared.
2) Function operation
2.1) When pressing Function selecting button, it follows the sequence specified below.
01: Test run → 02: Address setting → 03: Supply Air ESP → 04: Exhaust Air ESP →
05: Product Direction → 06: Quick refresh priority → 07: Master setting →
08: Override setting → 09: DryContact Auto → 10: Release of 3minute delay →
11: Zone stats → 12: Selecting °C or F → 13: Humidification for singular ventilation →
14: Humidification for Heat Mode Ventilation
※
Functions that are not contained in product do not appear.
2.2) Selected item LCD seg flickering (it keeps being flickering until set/cancel is pressed.)
2.3) Operation selection, wind strength, wind direction, extra operation, ventilation, reservation but-
ton is inputted, it is ignored.
3) Function operation and setting
3.1) Setting for each function, refer to the details for code.
3.2) When setting/cancel button is inputted, it is set and Seg flickering stops.
4) Function End
4.1) after 26 seconds without any input of relevant button (However, if relevant button (function set-
ting, up/down/right,light button, setting/cancel...) is inputted, it lasts for 25 seconds.)
4.2) Exit button
Field Setting and Test Run
Perform field setting with the remote controller